Gas Piping Installation
1. The installation must conform with local codes, or in
the absence of local codes with the National Fuel
Gas Code, ANSI Z223.1 or the CAN/CGA-B149,
Installation Codes.
2. Check Identification Nameplate for type of gas for
dryer.
3. Check for altitude elevation of dryer.
4. Check with utilities company for proper gas
pressure and gas supply line.
5. Natural Gas Only—Check the gas pressure inlet
supply to dryer, 11 inches water column (27.4 mbar)
maximum. Manifold Pressure—3.5 inches water
column (8.8 mbar) pressure.
6. L.P. Gas Only—Manifold pressure—13 inches water
column (32.4 mbar) maximum.
CAUTION: Low gas pressure and intermittent
gas will cause gas ignition problems and
inadequate drying of laundry.