Doc. SIE10166 Rev. 10 Page 20 of 28
. No 1 BSG1000 Main unit connected to the CBA1000 or CBA2000 breaker analyzer.
- N. 1 Nine-way connection cable of BSG Main Unit to CBA1000.
- N. 1 Three-way connection cable for synchronization.
- N. 1 Mains supply cable.
- N. 1 Grounding cable with crocodile.
Option characteristics:
. Number of main contact inputs (type BSG1000-1): 3, divided in three groups.
. Number of main contact inputs (type BSG1000-2): 6, divided in three groups of two each.
. Test current injection: 20 A dc nominal.
. Maximum test duration (each test): 1 s.
. Graphite nozzle test selection in the CBA1000 menu. In this instance, the contact with the graphite
is displayed as an intermediate thickness line. The relevant timings are reported.
. Mains supply:
.. From 85 to 265 V AC; 50-60 Hz,
.. From 100 to 350 V DC.
. Maximum supply current: 1 A @ 85 V AC.
Weights and dimensions
BSG1000 main unit
. Housing: aluminium case, with hinged removable cover and handles.
. Weight: 7 kg
. Dimensions: 325 x 180 x 285 (W x H x D)
BSG1000 measuring heads (three units)
. Housing: die-cast aluminium case.
. Weight: 0,7 kg (no cables)
. Dimensions: 125 x 56 x 125 (W x H x D)
The design below refers to the BSG1000-2 type.
Shop for Power Metering products online at:
1.877.766.5412