Quick Start           
  Copyright © ITECH Electronics Co., Ltd.  11 
2.  After the fuse box is opened, you can see the fuse in it. Please replace 
with a fuse of the same specification.. 
  
 
2.6 Output Checkout 
The following procedures check to ensure that the power supply develops its rated 
outputs and properly responds to operation from the front panel. 
2.6.1 Voltage Output Checkout 
The following steps verify basic voltage functions without load. 
1. Turn on the power supply. 
2. Enable the outputs 
Press      key to let the CV announciator turn on to light. 
3. Set the voltage value 
 Set some different voltage values, then wait till the Meter mode to check if the 
VFD displayed voltage value is the same as the set voltage value, and to check if 
the VFD displayed current value is nearly zero.   
4. Ensure that the voltage can be adjusted from zero to the full rated value.   
2.6.2 Current Output Checkout 
The following steps check basic current functions with a short across the power 
supply’s output. 
1. Turn on the power supply. 
2. Disable the output 
Press
key to ensure that the output is disabled. 
3. Connect a short across (+) and (-) output terminals with an insulated test lead. 
Use a wire size sufficient to handle the maximum current. 
4. Enable the output 
5. Adjust the voltage value to 1.0 volt 
 Adjust the voltage to 1.0 volt to ensure the power supply is in CC operation mode. 
The CC announciator will turn on. 
6. Adjust the current value 
Set some different voltage values, then wait till the Meter mode to check if the 
VFD displayed current value is the same as the set voltage value, and to check if 
the VFD displayed voltage value is nearly zero