Installation
Check that the maximum inlet pressure is not
higher than the design pressure of the regula-
tor.
Regulator should be lifted only with belts
around the body.
Arrange enough room for the serving of the
regulator.
Before installing the pressure regulator in the pip-
ing, the following must be checked:
The upstream and downstream flanges must
be parallel so as to install the regulator without
undue stress.
The upstream piping must be cleaned from all
impurities (sand, welding slag, etc.)
The pressure regulator must not be visibly
damaged.
The inlet and outlet chambers of the pressure
regulator must be perfectly clean.
Make sure that the direction of gas flow corre-
sponds to the arrow on the pressure regulator
body.
Installation position
The installation position is freely selectable.
Sensing line
The sensing line isn’t necessary of internal
pulse (< 4.0 bar)
For external pulse (> 4,0 bar), the sensing line
must be connected to a section reasonably
free from turbulences, preferably in a straight
section of the downstream piping (approx.
5D).
Connection: G1/2“/EO-12 (Regulator)
Connection: G1/4“/EO-6 (SSV)
Recommended pipe:
Ermeto-pipe EO-12 / -6, Steel, zinc protected
Breathing line
Breathing connection 133
G
3
/
4
Breathing connection 233/ 243/ 244:
G 1“
To realize fast load changes of the regulator,
the following cross section of breathing line is
to observe:
Up to 3 m breathing line, min. size
DN 20;
Longer than 3 m breathing line, size
DN 25
or larger.
Start-up instructions
To start-up the regulator after installation prop-
erly, proceed as follows:
Check that the upstream- and downstream
valves are closed;
Open the upstream valve slowly;
Reset the shut-off valve (see also page 15);
Check that the downstream pressure is rising
slowly on the downstream side manometer,
the downstream pressure should stop at the
closing pressure;
Open the downstream valves slowly to control
the even flow.
Regulator- and SSV-set point
The regulator is delivered according to the
specifications, specified in the purchase order.
If the adjusted outlet- / SSV shut off- pressure
is to be changed, proceed as follows:
Increasing the outlet- / shut-off pres-
sure:
The adjusting screw is to turn clockwise;
Decreasing the outlet- / shut-off pres-
sure:
The adjusting screw is to turn
anti-clockwise.