EasyManua.ls Logo

IXXAT CAN - Configuration of Error Detection and Repeater Off-time; Error Detection Bit Time Configuration; Repeater Off-Time Adjustment

IXXAT CAN
7 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Copyright IXXAT Automation GmbH
CAN Repeater - Manual, Version 3.6
4
> 500 kbps
> 100 kbps
> 5 kbps
Busabschluss
CAN 2
CAN 1
error shutdown
2µs
1µs
500ns
300ns
Sperrzeit
figure 4-1: Soldering jumper for activation of the bus
terminations, error shutdown, and repeater off-time
5. Configuration of the Error Detection
The separation of a defective network segment is made after reception of a
permanent dominant level for more than 20 bit times. The separated network
will be reconnected after reception of a recessive bit. The duration of the 20 bit
times depends on the soldering jumpers according to the figure 4-1. Only 1
Jumper must be closed.
The duration of the 20 bit times is measured of the data rate ratio of the
soldering jumpers. Please choose a bit rate jumper next to used bitrate. Default
configuration is a closed soldering jumper >5k Bit.
6. Configuration of repeater off-time
If CAN segments has a high capacitance load, discharge of CAN levels could not
be completed during the repeater off-time. This effects could arise at long cable
length or high number of CAN nodes. This could cause a disturbances on the
CAN network. For adoptions to such circumstances the repeater off-time could
be enlarged by soldering jumpers according figure 4-1.
Attention: Only one soldering jumper shall be closed. To enlarge the off-time of
the repeater also means to enlarge the round trip delay trough the repeater.

Related product manuals