P102 Start signal selection Factory Setting: 0
SettingRange:0-2Unit:1
Explanation: 0: Operation panel (FWD/REV/STOP)
1: I/O terminal
2: Communication (RS485)
Start signal selection are used to set running signal source.
0: Operation panel (FWD/REV/STOP)
Operation panel gives the running signal. The running of inverter can be
controlled by the Run/stop key (Forward reverse) key on the
operation panel. Press Run/stop key to stop running of inverter.
1: I/O terminal
In the initial setting ,the forward/reverse rotation signals are used as start and
stop signals .Turn on either of the forward and reverse rotation signals to start
the motor in the corresponding direction.
If both are turned off ( or on) during operation , the inverter decelerates to a
stop (or Keep the original running condition )
You can make two-wire type or three-wire type control mode by using I/O
terminal
Two-wire type
A two-wire type connection is shown below :
Parameter P102= 1 P315=6 P316=7