74
Default value 0.0
Automatic energy-saving selection
P413
Setting Range:0~100 Unit:1
P413 Automatic energy-saving selection
In constant-speed running of automatic energy-saving selection, best voltage
value may be calculated by loading condition and provided to load, in order to
achieve best energy-saving.
Attention: for running that load changes frequently or is almost at full load, this
function is not suitable.
F
Default value 0.0
Restart after instant power off
P416
Setting Range:0~1 Unit:1
Explanation: 0: Invalid: no restart after instant power failure
1: Valid: frequency tracing start-up
0: Invalid
Inverter clears the running command after power failure. After power is
recovered, inverter will not start automatically.
1: Frequency tracing enable
When power is shut-off in short time, inverter keeps the running command as
effective. When power is recovered in time, inverter will tracing the motor speed
and resume output.
Attention: when instant power failure restarting is enabled, inverter may start
the motor automatically. Please take care of the safety when use this function.