EasyManuals Logo

Janus Sv Series User Manual

Default Icon
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Page: 31
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Appendix A
MSDS101 Janus Fire Systems
Page 4
Material Safety Data Sheet
----------------------------------------------------------------------
HANDLING AND STORAGE
----------------------------------------------------------------------
Handling (Personnel)
Do not breathe gas. Avoid contact with eyes, skin, or clothing.
Wash thoroughly after handling. Wash clothing after use.
Storage
Store in a clean, dry place. Store below 52 C (126 F).
----------------------------------------------------------------------
EXPOSURE CONTROLS/PERSONAL PROTECTION
----------------------------------------------------------------------
Engineering Controls
Use only with adequate ventilation. Keep container tightly closed.
Personal Protective Equipment
EYE/FACE PROTECTION
Wear safety glasses or coverall chemical splash goggles.
RESPIRATORS
Wear NIOSH approved respiratory protection, as appropriate.
PROTECTIVE CLOTHING
Where there is potential for skin contact have available and wear
as appropriate impervious gloves, apron, pants, and jacket.
Exposure Guidelines
Exposure Limits
FM-200
AEL * (DuPont) : 1000 ppm, 8 & 12 Hr. TWA
* AEL is DuPont’s Acceptable Exposure Limit. Where governmentally
imposed occupational exposure limits which are lower than the AEL
are in effect, such limits shall take precedence.
----------------------------------------------------------------------
PHYSICAL AND CHEMICAL PROPERTIES
----------------------------------------------------------------------
Physical Data
Boiling Point : -16.4 C (2.5 F)
Melting Point : -131 C (-204 F)
Vapor Pressure : 65.7 psia @ 25 C (77 F) (453.3 kPa)
Liquid Density : 1.386 g/cm3 @ 25 C (77 F) (86.53 lb/ft3)
Critical temperature : 101.6 C (214.9 F)
Critical pressure : 424.7 psia (2930 kPa)
Odor : None.