5.6 SPECIAL OPERATING NOTES
5.6.1 During normal operation, when the High Pressure switch activates, the machine will restart
automatically when the head pressure drops below approximately 2500 Kpa.
5.6.2 When the Optional Pressure Control Circuit is installed and when the High-Pressure switch
activates, the machine must be cycled OFF and back ON for the compressor to restart. The “High
Pressure Cut Out” signal light (red) will illuminate when activated.
5.6.3 When the optional Press Control Circuit is installed and when low pressure switch activates
on completion of recovery, the machine must be cycled OFF and back ON for compressor to restart.
Green LED will illuminate when LP is activated.
5.6.4 When optional Low-Pressure Override is installed, compressor can be restarted after LP CUT-
OUT activation by pressing the black switch. This will allow to achieve a further vacuum beyond the
LP cutout range.
5.6.5 When optional Cylinder/Tank Overll Protection Device is installed and if the CT-OFD Cable is
not connected or Cylinder/Tank is full, the yellow “Cylinder Full” signal light will be illuminated. When
this is the case, the compression will start briey if the power is cycled OFF and ON again but will not
run for more than a few seconds. This is normal operation.
5.7 STORAGE
5.7.1 When the recovery process has been completed, carefully coil the Power Cord, the Refrigerant
Hoses and the Cylinder Overll Protection Cord (if used), ensuring that no dirt or foreign material is
left in the ends or on the connectors.
5.7.2 Place the recovery unit in the service vehicle in its upright position and store the hoses and
cords nearby. Provide reasonable care to place the unit where it will not be subjected to accidental
damage due to shifting items during transit or to heavier objects being placed on its top.
5.7.3 The unit can be stored safely in temperatures of 00 - 500 C and humidity levels up to 95%
RH. When stored in conditions that are severe, the unit may need to stabilize in the range 100
- 400C before it will oer optimum operating performance. For best results, store the unit in an
environmentally controlled area when not in use.
5.7.4 Always purge and vent the machine prior to storage, close V1 & V3 and leave V2 in the
Recover Position.