EDA-2040/ATP-2040 Electric Damper Actuator Installation Technical Bulletin 3
M
ounting
Standard
Observe ranges and limitations stated in the
Specifications section in the
EDA-2040/ATP-2040
Electric Damper Actuator Product Bulletin
in the
Damper and Actual Manual (FAN 268.1).
1. Verify that the damper blade is closed.
2. Place the actuator on the damper shaft so the
damper shaft protrudes through the actuator
coupler as shown in Figure 4.
VAV Box
(-) LO
OUT
GND
IN
UP
D
P
T
-
2
0
1
5
Damper
Shaft
Figure 4: Standard Mounting
3. Place the actuator in the desired mounting
position 1/8 in. (3.2 mm) from the mounting
surface (shown in Figure 5) so that the wiring
connections are easily accessible.
1/8 in.
Gap
1/4 in. Barbed Ports
for Field Supplied
Tubin
EDA-2040 Mounted
to VAV Box
CBL-2000 Cable Harness
for Connection to VAV
Controller
Note: Upper port
is
-
LO.
1/4 in. O.D. Tubin
DPT-2015-0
Quick Connect
Terminals
Figure 5: Actuator Position