RRS Economizer Controller Quick Start Guide 1
RRS Economizer Controller
Quick Start Guide
5292230-USG-B-0718
FIGURE 1 - RRS Economizer Controller
Field-installed economizer accessories with the RRS Econo-
mizer Controller utilize the P12/S12 connector for inter-con-
necting wiring to the 3 through 6 ton units equipped with
Simplicity Lite in the same manner as Honeywell W7212 and
Jade controllers in economizer accessories. Through the
P12/S12 connector, the unit-to-RRS Economizer wiring con-
nections are as follows:
TB1 to RRS Economizer Controller C pin - Pro-
vides cabinet ground-referenced 24 volts AC com-
mon to power the RRS Economizer Controller,
economizer inputs and outputs
Simplicity Lite G pin to RRS Economizer Con-
troller R pin - Provides 24 volts AC hot to power
the RRS Economizer Controller, economizer
inputs and outputs when Simplicity Lite operates
the indoor blower
Simplicity Lite OCC pin to RRS Economizer
Controller OCC pin - 24 volts AC originating from
jumper or thermostat input to the Simplicity Lite
OCC screw terminal, through the Simplicity Lite
OCC output pin to the RRS Economizer Controller
Simplicity Lite Y1 pin to RRS Economizer Con-
troller Y1 pin - 24 volts AC originating from ther-
mostat input to the Simplicity Lite Y1 screw
terminal, through the Simplicity Lite Y1 output pin
to the RRS Economizer Controller Y1 pin input
indicates there is a first stage cooling request
RRS Economizer Controller Y1O pin to Sim-
plicity Lite ECON pin - 24 volts AC from the RRS
Economizer Controller Y1O pin output to the Sim-
plicity Lite ECON pin input allows initiation of com-
pressor operation when outdoor conditions are
not suitable for free cooling
FIGURE 2 -
Simplified Diagram Of RRS Economizer
Control To 3 Through 6 Ton Unit Wiring
Connections
Y1
G
OCC
ECON
CR
Y2OY1O
Y2Y1
OCCW1
CR
DFBDMP
í +
24 VAC Common for Economizer
Controller Power/Inputs/Outputs
Simplicity Lite
TB1
On with Simplicity Lite blower operation – 24 VAC
Hot for Economizer Controller Power/Inputs/Outputs
From 24 VAC thermostat input to Simplicity
Lite – 1
st
Stage Cooling Request
From 24 VAC jumper/thermostat input to
Simplicity Lite – Occupancy Indication
24 VAC compressor request to Simplicity Lite with
1
st
Stage Cooling Request & Free Clg Avail = No

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls RRS Economizer Controller and is the answer not in the manual?

Johnson Controls RRS Economizer Controller Specifications

General IconGeneral
BrandJohnson Controls
ModelRRS Economizer Controller
CategoryController
LanguageEnglish

Related product manuals