5586996-JSG-A-0120 | Start-Up & Operation Guide
68
Table 26: Menus and Submenus (Continued)
Menu Submenu Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Commission
(Figure 28)
Standard
FanOnOcc (Continuous Fan Operation
in Occupied Mode) / Yes
Yes, No
Circ1ClgOATCutout (Circuit 1 OAT
Cooling Cutout) / 45.0°F
deg F (…75)
Circ2ClgOATCutout (Circuit 2 OAT
Cooling Cutout) / 45.0°F
deg F (…75)
Heat2CoolDly (Heat To Cool Delay) /
5 minutes
minutes (1–10)
Cool2HeatDly (Cool To Heat Delay) /
5 minutes
minutes (1–10)
Options
ExFType (Exhaust Type)
None, Barometric, Modulating Damper, Variable
Frequency Fan
ERV-En (ERV Enabled) No, Yes
Htg-En (Heating Mode Enabled for
Operation)
No, Yes
Htg-Type (Heating Control Type) None, Gas, Electric, Hot Water, Steam
HtgOATCutout-Sp (Outside Air Temp
Heating Cutout Setpoint) / 75.0°F
deg F (0–100)
DVent-Mode (Demand Ventilation Mode
of Operation, User to Setup)
Disabled, Controlled by IAQ, Diff between IAQ and
OAQ
MornW-En (Morning Warm-Up Enabled)
/ No
No, Yes
PIDTunRst (PID Tuning Reset) / False False, True
SafetySetup1 / Normal Normal, Pressurize, Depressurize, Purge, Shutdown
SafetySetup2 / Normal Normal, Pressurize, Depressurize, Purge, Shutdown
SafetySetup3 / Normal Normal, Pressurize, Depressurize, Purge, Shutdown
SafetySetupNI (Safety Setup Network
Input) / Normal
Normal, Pressurize, Depressurize, Purge, Shutdown
StagStrtEn (Staggered Start Enable) /
Enable
Disable, Enable
StagStrtOVRTime (Staggered Start
Override Time) / 0 seconds
seconds (0-1000)
ExDmprCtrlSrc (Exhaust Damper
Control Source) / None
None, Software, Hardware
EAD-O (Exhaust Damper % Command)
/ 0%
% (0–100)
ExFanCtrlSrc (Exhaust Fan Control
Source) / None
None, Software, Hardware
EF-O (Exhaust Fan VFD % Command)
/ 0%
% (0–100)
OADmprCtrlSrc (Outdoor Air Damper
Control Source) / None
None, Software, Hardware
OAPctOvr-Pos (Economizer Damper
Percent Over Position) / 0%
% (0–100)
Air Balance >
Supply
Air Balance Mode / Disable Disable, Enable
Export Air Balancing Report
UnitEn (Unit Enable) / Enable Shutdown, Enable
Auto Calibrate Now / OFF OFF, ON