Johnson Controls
Start-Up & Operation Guide | 5586996-JSG-A-0120
69
Operation
Table 26: Menus and Submenus (Continued)
Menu Submenu Parameters Displayed / Default
Conditions for Parameters Displayed
Units / Range
Commission
(Figure 28)
Air Balance >
Supply
MaxAirow cfm (0–100,000)
Econ (Economizer Damper %
Command)
%
OAPctOvr-Mode (Economizer Damper
Percent Override Mode) / OFF
OFF, ON
OAPctOvr-Pos (Economizer Damper
Percent Override Position) / 0%
% (0-100)
SF-O (Fan % Command) 0%
SFPctOvr-Mode (Supply Fan Percent
Override Mode) / OFF
OFF, ON
SFPctOvr-Pos (Supply Fan Percent
Override Position) / 0%
% (0-100)
Fr Air (Fresh Air Intake Value) cfm
MOAFlow-Sp (Fresh Air Intake Setpoint) cfm (0-50,000)
MOA-Range (Fresh Air Intake Max
Sensor Range)
cfm (0-750,000)
DA-P (Discharge Air Static Pressure) iwg
DctPrs-Sp (Duct Pressure Setpoint) / 1.5 iwg (0-5)
BldgPres (Building Static Pressure) iwg
Bldg-Sp (Building Pressure Setpoint) iwg (-0.25 to 0.25)
Supply Flow Value cfm
Supply Pickup Gain 0–100
Supply Area square feet (0–100)
Altitude feet (-1,500 to 30,000)
SZVAVClgMinFan (SZVAV Cooling
Minimum Fan Speed)
% (20–67)
SZVAVHtgMinFan (SZVAV Heating
Minimum Fan Speed)
% (20–67)
SZVAVMinFanSpd (SZVAV Minimum
Fan Speed)
% (20–67)
HighSpeedFan-MinPos (Economizer
Damper Minimum Position High Speed
Fan) / 5%
% (0–100)
LowSpeedFan-MinPos (Economizer
Damper Minimum Position Low Speed
Fan) / 25%
% (0–100)
SF-LowSpd-SP (Supply Fan Low Speed
Threshold) / 50%
% (0–100)
DVentMaxEconPos (Demand Ventilation
Maximum Economizer Position) / 50%
% (0–100)
MaxOAFlow (Maximum Outside Airow) cfm (0–100,000)
Air Balance >
Return
Air Balance Mode / Disable Disable, Enable
Export Air Balancing Report
UnitEn (Unit Enable) / Enable Shutdown, Enable
RAD-O (Return Air Damper Command) %
RFPctOvr-Mode (Return Fan Percent
Override Mode)
OFF, ON

Table of Contents