Field Wiring Inputs and Outputs
Unit Shut Down (Emergency Stop) Input
Occupancy Input
Zone Temperature Input
VAV Heat Relay Output
Occupancy Indication Output
Alarm Output
Pump Start Output
Standard Control Sequences
Unit can be indexed between Occupied and Unoccupied via four methods:
1. Manually via OFF-AUTO-ON switch
2. Remotely via Field Wiring Input
3. Remotely via Building Automation System (BAS) (BACnet
®
or Modbus
)
4. Automatically via internal scheduling
Control sequences for constant volume (CV), VAV, and Flexsys
(Underoor VAV)
built in.
For VAV operation, four Supply Air Temperature setpoint reset sequences can be
selected:
1. No Reset, fixed Supply Air Temperature setpoint
2. Reset via Return/Zone Temperature
3. Reset via Outside Air Temperature
4. Reset via VFD Speed
Occupied Heating
Unoccupied Heating (Night Set Back)
Morning Warm-up
Economizer Sequences Built-In
1. Waterside Economizer with Adjustable Approach setpoint
2. Airside Dry Bulb (Units Equipped with Mixing Box)
3. Airside Single Enthalpy (Units Equipped with Mixing Box)
4. Airside Dual Enthalpy (Units Equipped with Mixing Box)
Note: Economizer sequences allow for economizing with mechanical cooling when