Inputs Universal software configurable
Input Types:
Digital: Dry Contact
Pulse: Dry Contact
Analog Voltage: 0 to 10 VDC, Accuracy: ±0.5%,
Analog current: 4 to 20 mA with 249 ohmsexternal resistor (wired in parallel)
Resistor Support:
Thermistor: Type 2, Type 3 10k ohms (10k ohms at 25ºC [77ºF])
Range: -40 to 150ºC (-40 to 302ºF)
Platinum:
Pt1000: (1k ohm at 0ºC [32ºF])
Range: -40 to 150ºC (-40 to 302ºF)
PT100: 100 ohms (1k ohm at 0ºC [32ºF])
Range: -40 to 135
ºC (-40 to 275ºF)
Nickel:
Ni1000 (1k ohm at 0ºC [32ºF])
Range: -40 to 150
ºC (-40 to 302ºF)
Potentiometer: Translation table configurable on several points
Input Resolution: 16-bit analog/digital converter
Outputs Universal 0 to10 VDC, digital 0 to12 VDC (on/off), 0-20 mA, PWM, or floating
1
PWM output: adjustable period from 2 seconds to 15 minutes
Floating control: requires two consecutive output
minimum pulse on/off: 500 milliseconds
adjustable drive time period
60 mA maximum at 12 VDC (60ºC; 140ºF)
Minimum load 200 ohms
Auto reset fuse
60 mA at 60
°C (140°F)
100 mA at 20
°C (68°F)
Output Resolution: 10-bit digital/analog converter
Power Supply Output: 15 VDC, maximum 240 mA
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and
light-industrial environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
light-industrial environments.
Compliance United States: UL Listed: UL916 Energy management equipment
Material: UL94-5VA
Canada: UL Listed: UL916 Energy management equipment
Material: UL94-5VA
1. Available when programmed with LN GPI software.
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.