TEC1100 Series Thermostat
In this document, Building Automation System (BAS) is a generic term
that refers to the Metasys® Network (Network Control Module [NCM] or
N30 series), Companion, and Facilitator® supervisory systems. When you
refer to system specific applications, use the specific system names.
The TEC1100 Series includes three nonprogrammable models:
single-stage (TEC1101), heat pump (TEC1102), and multistage
(TEC1103). The applications include furnace, air conditioner, heat pump,
and rooftop units. The TEC1100 incorporates fuzzy logic for precise
control in a thermostat type package.
All TEC1100s have Metasys N2 communication capability. This
communication allows the user to view and adjust parameters from a
remote workstation. It also provides information, such as outdoor air
temperature, to the TEC1100 units on the bus. The thermostat is easy to
operate and normally displays room temperature and mode of operation
using Cooling ( ) or Heating ( ) icons. When there is a call for cooling,
the Snowflake icon ( ) blinks. Likewise, during a call for heating, the
Flame icon ( ) blinks. When the temperature is satisfied, neither icon
blinks. In the Auto mode, both icons ( ) appear continuously when
satisfied. Light-Emitting Diodes (LEDs) on the top of TEC1102/1103
models use Binary Inputs (BIs) to indicate a clogged filter and external
service. A unique temperature alarm (BI 2) indicates that the zone
temperature has not been satisfied in 45 minutes.
Introduction
Description

Questions and Answers

  • J
    Justin WolfAug 9, 2025
    What to do if Johnson Controls METASYS TEC1101 Thermostat TEC1100 does not come online?
    • J
      justinjohnsonAug 10, 2025
      If your Johnson Controls Thermostat TEC1100 fails to come online, several factors could be responsible: * A duplicated address. The solution is to change each duplicate address to a unique number. * Too many devices on the N2 Bus. Keep in mind the maximum number of N2 devices allowed on the N2 Bus: 100 devices per NCM, 32 devices per N30, 32 devices per N31, 150 devices per the Companion/Facilitator system. * The TEC1100 isn't receiving power. Apply power to the TEC1100. * Broken N2 cable runs. Locate and correct the wiring. * Incorrect device type. The TEC1100 address must be VND device type.
  • J
    Jonathan ReynoldsAug 18, 2025
    Why does my Johnson Controls Thermostat TEC1100 cycle online and offline?
    • C
      Calvin WilliamsAug 18, 2025
      If your Johnson Controls Thermostat TEC1100 is cycling online and offline, here's what might be happening: * Two or more controllers have the same address. To fix this, change each duplicate address to a unique number. * There are ‘Y’ or ‘T’ taps, or the repeater lost power or is wired incorrectly. For this, refer to the N2 Communications Bus Technical Bulletin (LIT-636018).
  • D
    Deanna WilsonAug 29, 2025
    How to fix entire N2 Bus offline on Johnson Controls METASYS TEC1101?
    • C
      chapmanjohnAug 29, 2025
      If the entire N2 Bus is offline on your Johnson Controls Thermostat, consider these potential causes: * EOL jumpers on MM-CVT101 or NCM are not installed. Install the EOL jumpers properly. * MM-CVT101 is not plugged into a Personal Computer (PC) or a 120 VAC source. Plug the MM-CVT101 into a PC or a 120 VAC source. * Wiring near the BAS is broken. Repair the wiring. * No point mapping entered. Define the BAS database.

Summary

Introduction

Description

Details of TEC1100 series models, N2 communication, and operation.

Installation

Mounting the TEC1100 Series Thermostat

Instructions for mounting the TEC1100 thermostat on an interior wall.

Wiring the TEC1100 Series Thermostats

Setting the DIP Switches

TEC1101 Single-Stage DIP Switch Settings

Details DIP switch selections for TEC1101 single-stage models.

TEC1102 Heat Pump DIP Switch Settings

TEC1103 Multistage DIP Switch Settings

N2 Bus Connections

Connecting to NCM Series

Details on connecting the TEC1100 thermostat to a Network Control Module (NCM).

Setting the N2 Address

TEC1100 Features

Commissioning

Troubleshooting

N2 Bus Configuration Troubleshooting

Table listing possible causes and solutions for N2 bus configuration issues.

Occupant Complaints Troubleshooting

TEC1100 Thermostat Troubleshooting

Table detailing symptoms, possible causes, and corrective actions for thermostat issues.

Johnson Controls METASYS TEC1101 Specifications

General IconGeneral
ModelTEC1101
ManufacturerJohnson Controls
DisplayLCD
Power Supply24 VAC
ApplicationHVAC
Communication ProtocolN2 Bus
MountingWall Mount
Setpoint AdjustmentLocal
CompatibilityMETASYS System