Pneumatic Control Manual 717.1
Room Devices Section
Technical Bulletin T-4000
Issue Date 0984
© 1984 Johnson Controls, Inc.
1
Code No. LIT-7171089X
T-4000 Series Room Thermostat
Adjusting Instructions*
The T-4000 Series Pneumatic
Room Thermostats are factory
calibrated to the values specified
in Table 1. If these settings are
suitable to the application, no
adjustments need to be made. If
different settings are required,
turn the set point dial to the
desired value.
If the room temperature is out of
control, determine the cause of
the problem. Possible causes
not involving the thermostat are
listed below.
1. Check for proper operation
of the controlled device.
2. Check to see if the controlled
medium (water, for example)
is hot or cold enough to
maintain the desired
temperature.
3. Check for unusual or
extreme loads in the space
which may overcome the
efforts of the thermostat to
maintain control.
If it is determined that the
thermostat is out of adjustment,
follow the appropriate instructions
to recalibrate the instrument.
Sensitivity Adjustment
(See Fig. 1)
All T-4000 series thermostats
have an integral output pressure
test port. The newer high volume
output thermostats have a plug-in
test port fitting which accepts a
hypodermic needle test probe
and gage (X-200-140 and G-
2010-11). On older models, the
test port cap screw must be
removed to accept a screw-in
test gage (X-200-19). For these
units, a test port fitting (T-4000-
615) can be ordered. All low
volume output thermostats have
hypodermic needle test points.
For units that require a screw-in
gage, remember to replace the
test port cap screw after
adjustment.
The sensitivity of the T-4000
series instruments is factory set
at 2.5 PSI/F
°
(32 kPa/C
°
). It is
adjustable from 1 to 3 PSI/F
°
(13 to 38 kPa/C
°
) for low volume
output thermostats and from .
75 to 4 PSI/F
°
(10 to 51 kPa/C
°
)
for high volume output
thermostats. (Sensitivity of the T-
4003 is fixed at 2.5 PSI/F
°
).
1. Furnish the appropriate
supply pressure to the
instrument.
2. Insert the appropriate gage.
3. Note the output pressure.
Note:
The output pressure
for T-4054 thermostats must
be within one of the two
control ranges (not within the
deadband range).
4. For high volume output
thermostats, move the
sensitivity slider toward the
control port to increase or
away from the control port to
decrease the sensitivity. For
low volume output
thermostats, move the
sensitivity slider down to
*
This bulletin provides adequate instructions for making basic adjustments to
T-4000 series room thermostats. For more detailed information, contact the local
branch office.
Archived Document

Other manuals for Johnson Controls T-4002

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls T-4002 and is the answer not in the manual?

Johnson Controls T-4002 Specifications

General IconGeneral
ProgrammableNo
Hold FeatureNo
Sensing ElementBimetallic element
Operating Pressure20 psi
StagesSingle Stage
CompatibilityCompatible with pneumatic control systems

Summary

T-4000 Series Room Thermostat Adjusting Instructions

Sensitivity Adjustment for T-4000 Series

General procedure for adjusting the sensitivity of T-4000 series thermostats using test ports and sliders.

T-4003 Range of Remote Readjustment

Specific instructions for adjusting the remote readjustment range on T-4003 models.

Set Point Adjustment Procedures

T-4002 and T-4100 Set Point Adjustment

Detailed steps for setting the point for T-4002 and T-4100 thermostats.

T-4003 Set Point Adjustment

Instructions for adjusting the set point of T-4003 thermostats.

T-4054 Deadband and Set Point Adjustments

T-4054 Deadband Setting

Procedure for checking or resetting the deadband setting on T-4054 models.

T-4054 Set Point Calibration

Steps for calibrating the set point on T-4054 thermostats.

Specific Model Set Point Adjustments

T-4110 Set Point Adjustment

Instructions for adjusting the set point on T-4110 thermostats.

T-4506 and T-4516 Set Point Adjustment

Guide for setting day and night points on T-4506 and T-4516 models.

T-4600 and T-4756 Adjustment Procedures

T-4600 Heating and Cooling Set Point Adjustment

Steps for adjusting heating and cooling set points on T-4600 thermostats.

T-4756 Heating and Cooling Set Point Adjustment

Procedure for adjusting heating and cooling set points on T-4756 thermostats.

Switchover Point Adjustment

Switchover Point Adjustment for T-4506, T-4516, T-4756

Instructions for resetting the switchover point between supply pressures for specific models.