EasyManua.ls Logo

Johnson Controls T-901 - User Manual

Johnson Controls T-901
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Pneumatic Control Manual 717.1
Repair Parts for Discontinued Products Section
Instruction Bulletin T-901-A
Issue Date 16B4
© Johnson Controls, Inc.
1
Code No. LIT-7171715X
T-901, T-903 and T-905
Submaster Thermostats
Operation
This series of submaster thermostats is so designed
that the set point may be remotely readjusted by
changing pressure to the readjusting bellows.
(See Fig. 2)
A master-submaster system consists of a primary
controller (master thermostat) and submaster
thermostat so connected that output (master
pressure) from the master thermostat readjusts the
set point of the submaster thermostat according to a
predetermined schedule. A dial on the submaster
thermostat also provides manual selection of set
point at the instrument. These thermostats are
available with liquid filled remote-bulb-and-capillary,
insertion and immersion measuring elements.
Control Action
These thermostats are available in two-position and
proportional action models. Both models are
furnished either direct or reverse acting. A direct
acting thermostat increases control pressure when
temperature increases. A reverse acting thermostat
decreases control pressure when temperature
increases. A simple change of pivots converts the
thermostats from one action to the other. See Fig. 1
and Table I.
Readjusting Action
Depending on the pivots used, an increasing master
pressure either raises or lowers the set point. When
increasing master pressure raises set point, the
thermostat has direct readjustment. When increasing
master pressure lowers set point, the thermostat has
reverse readjustment.
Sensitivity
Sensitivity of a pneumatic thermostat is defined as
the change in the control air pressure per unit change
in temperature. It is expressed as psi per degree.
Sensitivity of this series is adjustable from 1/8
through 5 psi per degree by moving a slider located
on the control mechanism channel.
Differential
Differential of a two-position controller is defined as
the degrees temperature change required to actuate
the relay. The sensitivity adjustment described above
becomes a differential adjustment in two-position
action. Differential is adjustable 2 through
30 F degrees.
Operation of Control Mechanism
The liquid in the measuring element expands or
contracts with temperature changes. This movement
is transmitted to the control port lid through a system
of levers as shown in Fig. 2. Output pressure to the
controlled device varies with control port lid
Fig. 1: T-901 Series Submaster
Thermostat Showing Pivot Locations
Question and Answer IconNeed help?

Do you have a question about the Johnson Controls T-901 and is the answer not in the manual?

Johnson Controls T-901 Specifications

General IconGeneral
Power Source24 VAC
Stages1 Heat/1 Cool
MountingWall mount
ColorWhite
Terminal DesignationsR, W, Y, G
CompatibilityConventional HVAC systems

Summary

Operation of Submaster Thermostats

Control Action

Thermostats offer two-position or proportional action, with direct or reverse acting.

Readjusting Action

Master pressure changes set point; direct raises, reverse lowers it.

Sensitivity

Sensitivity is psi/degree, adjustable from 1/8 to 5 psi/degree.

Differential

For two-position controllers, degrees change to actuate relay, adjustable 2-30°F.

Operation of Control Mechanism

Liquid expansion/contraction moves levers, varying output pressure via control port lid.

Operation of Readjusting Mechanism

Stops for Readjustment Mechanism

Adjustment Procedures

Setting Range of Remote Readjustment

Adjusts remote readjustment range using a dial calibrated in °F for master pressure change.

Checking the Range of Remote Readjustment

Procedure to verify and set the remote readjustment range against master pressure.

Adjusting the Set Point

Adjusting the Stops

Related product manuals