EasyManua.ls Logo

Johnson Controls SABROE ComPAC - Valve Positions During Operation, Compac

Johnson Controls SABROE ComPAC
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating manual - ComPAC
42/56
011769 en 2020.03
Operating instructions
5.3.3 Valve positions during operation, ComPAC
(water-cooled condenser)
Pos. no.
Designation Position during operation
400
Compressor unit valves
Please see the compressor manual
401
Compressor suction stop valve
Open
402
Compressor discharge stop valve
Open
410
Ball valve - heat recovery Closed
41
Ball valve - heat recovery Closed
412
Ball valve
Open
413
Ball valve
Open
417
Double stop valve One outlet open / one outlet closed
418
Safety relief valve (Closed) Fixed set point
419
Safety relief valve (Closed) Fixed set point
420
Double stop valve One outlet open / one outlet closed
421
Safety relief valve (Closed) Fixed set point
422
Safety relief valve (Closed) Fixed set point
423
Charge valve (R717) Closed
424
Stop valve for oil recovery
Open
425
Stop valve for oil recovery
Open
430 Stop valve - expansion Open
431
Stop valve for oil return
Open
432
Stop valve for oil recovery / oil return
Open
440
Stop valve for oil recovery
Open
441
Float valve - expansion Opens automatically
442 Stop valve Closed
443
Stop valve Closed
444
Drain valve Closed
Table 1: Valve positions during operation, ComPAC

Table of Contents