T600HPx-4 and T600HPx-4+PIR Series Heat Pump Thermostat Controllers Installation Instructions10
Fan cont Determines how the fan is activated
in response to a call for heating.
Default: on
Note: The Fan cont parameter
applies to W1 when the fan is in the
Auto mode only. The Fan cont
parameter does not affect fan
operation on a call for cooling (Y1).
(off): The thermostat controller does not activate the fan in
response to a call for heating. The fan is activated by the equipment
fan and limit control.
(on): Enables the thermostat controller to activate the fan in
response to a call for heating.
Fan del Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
Note: The fan delay is only active
when the fan is in the Auto mode.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
TOccTime Sets the duration of the Temporary
Occupancy Time (when the
thermostat controller is in the
Unoccupied mode) when a
Schedule Override Function is
enabled using either the Main User
Menu or DI1 or DI2 configured as a
temporary override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN arrow keys.
Default: 3.0 hrs
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Cal RS Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Cal OS Sets the desired outside air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
HP stage Sets the number of heat pump
compressor stages.
Default: 2.0
Note: Reverts the operation of a
two-stage thermostat controller to a
one-stage thermostat controller
when the second cooling stage is
not needed.
(1.0): One Stage
(2.0): Two Stages
Table 2: Installer Configuration Menu (Part 4 of 7)
Parameter
Appearing
on Display
Description and Default Selection Options