PARAMETER SETTING (PART 2/2)
Code
T9600-
TF20-
1JS0
T9603-
T000-
1JF0
T9601-
TF20-
1JS0
T9600-
TF21-
1JS0 Parameter Name Default Function
16
KEY-LOCK 00
Key lock function:
00: No Lockout
01: Level 1 ->Lock all keys
02: Level 2 ->Lock the keys except Fan Speed and Temp
Adjustment keys
03: Level 3 ->Lock the ON/OFF and Clock keys
04: Level 4 ->Lock the keys except ON/OFF key
17
TEMP-DISP 00
UI display room temperature or set point:
00: Room Temperature
01: Setpoint
18
UNIT 01
Unit selection:
00: IP
01: SI
19
DAMP-OPEN-TIME 0
Damper opening time, for AHU application
range 0-99 (0=75 s, 99=174 s)
20
SF-VERSION Software version, read only
SERVICE SETTING (Setting through professional)
In the Setting page press
button for 3 seconds to get in Service page, the occupancy icon shows. Press to scroll forward and M button to
scroll backward in the list and use
and
button to change parameter value. For T9603-T000-1JF0, press and hold for 3 seconds to access
the parameter list and press to scroll foward through the list.
PARAMETER SETTING (PART 1/2)
Code
T9600-
TF20-
1JS0
T9603-
T000-
1JF0
T9601-
TF20-
1JS0
T9600-
TF21-
1JS0 Parameter name Default Function
02
FRST-PRT 00
Frost protection:
00: No
01: Yes
03
FH-FAN 00
Enable/disable fan output when floor heater
00: Disable
01: Enable
04
APPLICATION 00
T9600- TF20-1JS0:
00: 2pipe FCU (relay)
01: 4pipe FCU (relay)
02: 2pipe 3 wire (relay)
03: 2pipe FCU (relay) with floor heating
04: 2pipe FCU (relay) with TiO2/ESP
05: water source heat pump
T9601- TF20-1JS0:
00: 2-pipe FCU (relay), ECM fan
01: 4-pipe FCU (relay), ECM fan
02: 2-pipe 3 wire (relay), ECM fan
03: 2-pipe FCU with floor heater, ECM fan
04: 2-pipe FCU with TiO2/ESP, ECM fan
05: water source heat pump, ECM fan
06: 2-pipe FCU (prop), ECM fan
07: 2-pipe FCU (prop) with floor heater, ECM fan
08: 2-pipe FCU (prop) with radiator, ECM fan
09. AHU
T9600- TF21-1JS0:
00: 2-pipe FCU, three speed fan
01: 4-pipe FCU, three speed fan
05
DOWN-SET-LIMIT
5°C/
41°F
lower setpoint limit
Range: 0°C~36°C (32°F-97°F)
06
UP-SET-LIMIT
35°C/
95°F
Upper setpoint limit
Range: 2°C~37°C (36°F~99°F)
07
FP-SP
5°C/
41°F
Frost protection setpoint.
Step: 0.5°C (1°F)
Range: 0°C~20°C (32°F-68°F)
08
ECM-MIN-V 3 V
ECM Min voltage.
Min voltage below which the fan output is 0%.
Step: 0.5 V
Range: 0 V~10 V