TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
16
UI3 Configuration of Universal Input 3.
Default: None
(None): No function is associated with an input.
(COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water
changeover switching. Valid only for two-pipe systems.
A water temperature greater than 78.0°F (25.6°C) indicates hot
water is present.
A water temperature less than 75.0°F (23.9°C) indicates cold
water is present.
Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between
Cooling Only and Heating Only. The changeover sensor does not
operate in Cooling and Reheat, Heating and Reheat, or Cool/
Heat Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring
MenuScro Gives the option of having the
display continuously scroll the
parameters.
Default: on
(on): The scroll is active.
(off): The scroll is inactive.
AutoMode Enables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat cover.)
Default: on
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
C or F Provides temperature scale options
for display.
Default: °F
(°F): Fahrenheit scale
(°C): Celsius scale
%RH dis Displays the current humidity
reading (TEC2236-4, TEC2236H-4,
TEC2236H-4+PIR, TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR models).
Default: off
(on): Display%RH
(off): No display of%RH
Lockout Selectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
Lock
out
Level
Function
System
Mode
Setting
Fan Mode
Setting
Unoccupied
Override
Occupied
Temperature
Setpoints
(0) Access Access Access Access
(1) Access Access No Access Access
(2) No Access No Access Access Access
(3) No Access No Access No Access Access
(4) No Access No Access Access No Access
(5) No Access No Access No Access No Access
Table 5: Installer Configuration Menu (Part 2 of 8)
Parameter
Appearing
on Display
Description and Default Selection Options

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC2216H-4 and is the answer not in the manual?

Johnson Controls TEC2216H-4 Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC2216H-4
CategoryThermostat
LanguageEnglish

Related product manuals