TEC3000 Series Proportional Fan Coil
Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostat Controllers
are stand-alone and field-selectable BACnet
®
MS/TP or
N2 networked devices. Wireless networked models of the
TEC3000 Series Thermostat Controller are also available.
Proportional Fan Coil and Individual Zone Thermostat
Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV)
equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or
floating control input
The networked models feature a field-selectable
Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring
and programming for efficient space temperature control.
The wireless models (TEC30xx-xx-000) are compatible
only with the WNC1800/ZFR182x Pro Series Wireless Field
Bus System that enables communication with a building
automation system (BAS). The new wireless models
(TEC31xx-14-000) are compatible only with WRG1830/
ZFR183x Pro Series Wireless Field Bus System. All models
include a USB port configuration that reduces installation
time to allow simple backup and restore features from a
USB drive, which enables rapid cloning of configuration
between similar units.
Some models have occupancy sensing capability built into
the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial
buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI
with backlit display that makes setup and operation quick
and easy. For Single-or Two-Stage Economizer Thermostat
Controller models, only the single-speed fan configuration
is supported. For TEC3x1x and TEC3x2x models, multiple
fan configurations are supported for fan coil equipment
types, as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe
fan coil units with reheat, and four-pipe fan coil units
with or without reheat. When no heating is required,
the thermostat controller monitors space humidity and
activates dehumidification control as necessary. Heat
and/or reheat is used as required to maintain the space
temperature. For optimal dehumidification performance,
use a fan coil unit that has a multi-speed or variable-speed
fan (VSF).
Important: The TEC3000 Series Thermostat
Controller is intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of
or protect against failure or malfunction of the
thermostat controller.
Important: Le TEC3000 Series Thermostat Controller
est destiné à transmettre des données entrantes
à un équipement dans des conditions normales
de fonctionnement. Lorsqu'une défaillance ou un
dysfonctionnement du thermostat controller risque
de provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des
dispositifs de protection supplémentaires.Veiller
dans ce cas à intégrer de façon permanente d'autres
dispositifs, tels que des systèmes de supervision
ou d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement
ou de protection en cas de défaillance ou de
dysfonctionnement du thermostat controller.
North American emissions
compliance
United States
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in
a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception,
which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV
technician for help.
LIT-12013162
2020-12-15
TEC3322-1x-xxx, TEC3323-1x-xxx, TEC3622-1x-xxx,
TEC3623-1x-xxx, TEC3022-1x-xxx, TEC3023-1x-xxx,
TEC312x-14-xxx

Questions and Answers

Johnson Controls TEC3630-14 Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3630-14
CategoryThermostat
LanguageEnglish

Summary

Applications of TEC3000 Series Thermostats

North American Emissions Compliance

United States Emissions Compliance

Equipment tested and found to comply with FCC rules for digital devices, designed to provide protection against RF interference.

Canada Emissions Compliance

Apparatus meets Canadian Interference-Causing Equipment Regulations for Class B digital apparatus.

Installation Guide

Parts Included in Installation

Lists the components provided with the TEC3000 Series Thermostat Controller for installation.

Location Considerations for Installation

Guidelines for selecting an optimal location for the TEC3000 controller, considering environmental and signal factors.

Installing the Thermostat Controller

Step-by-step instructions for physically mounting and connecting the TEC3000 thermostat controller to a wall or junction box.

Wiring Procedures

Terminal Identification Reference

Wiring Diagrams Overview

Setup and Adjustments

Overview of Home Screen Interface

Introduces the home screen interface and customization options for the TEC3000 thermostat controller display.

Customizing the Home Screen Display

Details on changing themes, enabling backlight, and selecting which elements to display on the home screen.

Touchscreen Icons

User Lockout Levels

Using the USB Port for Operations

Loading Firmware via USB

Step-by-step guide for updating the TEC3000 controller's firmware using a USB drive.

Managing Settings via USB

Instructions for backing up and restoring TEC3000 controller configurations and settings using a USB drive.

Choosing the Communication Mode

Configuration steps for setting the communication protocol (BACnet or N2) for networked TEC3000 models.

Thermostat Configuration

Screen Timeout and Reset Settings

Information on how the screen times out and how to disable the screensaver function.

Selecting the Unit Type

Guide on configuring the TEC3000 for different unit types: four-pipe, two-pipe, or VAV systems.

Setting the Control Mode

Instructions to set the control mode (Cooling, Heating, or Auto) based on zone temperature and setpoints.

Configuring Supply Fan and Fan Mode

How to configure supply fan types, speeds, and operating modes for fan coil units.

Configuring Zone Space and Equipment Size

How to adjust the equipment size parameter for optimal temperature response in different zone conditions.

Changeover Configuration

Settings for system changeover detection between heating and cooling modes based on various sensors.

Dehumidification Control Configuration

Steps to enable and configure dehumidification control for specific fan coil unit configurations.

Temperature Setpoints Configuration

How to set and adjust various temperature setpoints for occupied, unoccupied, and standby modes.

Occupancy and Scheduling

Selecting Schedule Source

How to choose between local or BAS for the occupancy schedule source for networked models.

Setting the Local Schedule

Step-by-step guide to set up a weekly occupancy schedule with up to four events per day.

Enabling Optimal Start Algorithm

How to enable the optimal start algorithm for energy-efficient zone pre-heating or pre-cooling.

Enabling the Motion Sensor

Steps to enable and configure the motion sensor for automatic occupancy adjustments.

Configurable Binary Inputs

Auxiliary Control Configuration

Commissioning Mode

Scheduled Circulation

Configurable Analog Inputs (AIs)

Configuring the Analog Inputs

Steps to connect sensors and configure analog inputs (AI1, AI2) for various sensor types.

Networked Sensors Integration

Information on using sensor values supplied over a network connection for the TEC3000.

Available Fault Diagnostics

Troubleshooting

TEC3000 Series Technical Specifications

Technical Specifications Summary

Key electrical, environmental, and performance specifications for the TEC3000 controller.

Repair and Warranty Information

Guidance on product repair, warranty details, software terms, and patents.

Contact Information

Single Point of Contact by Region

Contact details for Johnson Controls in APAC, Europe, and NA/SA regions.

Local Branch Office Contact

Information on how to find and contact local Johnson Controls branch offices.

Related product manuals