TEC3000 Series Wireless Proportional Fan Coil and Individual Zone
Thermostat Controllers with Dehumidification Capability
Installation Instructions
1
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers are wireless
networked devices that provide control of the following:
local hydronic reheat valves
pressure-dependent variable air volume (VAV) equipment with or without local reheat
two- or four-pipe fan coils
cabinet unit heaters
other individual zone equipment using a proportional 0 to 10 VDC control input
The networked models are compatible with the WNC1800/ZFR182x Pro Series Wireless Field Bus System that
enables remote monitoring and programming for efficient space temperature control. All models include a USB port
configuration that reduces installation time by allowing simple backup and restore features from a USB drive, which
enables rapid cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive UI with backlit display that makes setup and operation quick and easy. Multiple fan
configurations are supported for fan coil equipment types:
single-speed
multi-speed (two or three discrete speeds)
variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the thermostat controller monitors space humidity and activates
dehumidification control as necessary. Heat and reheat is used as required to maintain the space temperature. For
optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
TEC3000 Series Wireless Proportional Fan Coil and
Individual Zone Thermostat Controllers with
Dehumidification Capability
Installation Instructions
TEC3020-xx-xxx, TEC3021-xx-xxx, TEC3022-xx-xxx, TEC3023-xx-xxx
Part No. 24-10788-19, Rev.
D
Issued July 2018
*241078819D*
24-10788-19, Rev. D
(barcode for factory use only)

Questions and Answers

  • K
    Keith RobertsSep 5, 2025
    What to do if Humidity is Unreliable on Johnson Controls Controller?
    • D
      danielsolomonSep 5, 2025
      If your Johnson Controls Controller shows 'Humidity Unreliable,' it means the zone humidity reading was reliable but has now failed. Here's how to address it: 1. If the source of zone humidity was the onboard sensor, contact Johnson Controls product sales and support. 2. If the source of zone humidity was a BAS, check the BAS to ensure it's still online and providing the TEC with the humidity reading. If removing the BAS mapping was intentional, reset sensors through the menu.
  • H
    Hailey WattsSep 6, 2025
    What does Supply Fan Fault mean on my Johnson Controls TEC3011?
    • S
      Scott Scott MDSep 6, 2025
      If your Johnson Controls Controller displays a 'Supply Fan Fault', it means the supply fan status configured for either BI1 or BI2 hasn't been proven within the configured fan alarm delay. To resolve this: 1. Verify that the supply fan is operating when turned on. 2. Verify that the supply fan status wiring is connected correctly.
  • R
    Raven WilliamsSep 6, 2025
    How do I resolve a Firmware Mismatch error on my Johnson Controls TEC3011?
    • D
      david02Sep 7, 2025
      If you encounter a 'Firmware Mismatch' error on your Johnson Controls Controller, it indicates that a previous upgrade or downgrade process did not complete successfully. Here’s how to address it: * If the previous upgrade didn't complete, upgrade the TEC3000 to the latest released version and then upgrade it to the current version again. * If a previous downgrade didn't complete because the previous version is no longer supported, reboot the TEC3000 to clear the fault.

Summary

Applications

Installation

Location Considerations

Installing the Thermostat Controller

Wiring

Setup and Adjustments

Using the USB Port

Loading the Firmware

Step-by-step guide for updating the thermostat controller's firmware using a USB drive for performance improvements.

Restoring the Settings

Backing Up the Settings

Instructions on how to save the thermostat controller's current configuration settings to a USB drive for backup.

Configuring the Thermostat Controller

Configuring the Supply Fan - Fan Coil Only

Setting the Control Mode

Changeover

Dehumidification Control - Fan Coil Only

Temperature Setpoints

Configuring Occupancy

Selecting Schedule Source

Setting the Local Schedule

PID;PRAC+ Automatic Control Tuning

Commissioning Mode

Available Fault Diagnostics

Lists various fault conditions and diagnostic capabilities supported by the controller for troubleshooting.

Menus and Submenus

Schedule Options

Control Setup

Configuration parameters for control mode, unit enable, and fan mode for operational settings.

Control Setup (Cont)

Network Setup

Equipment Setup

Setup parameters for unit type, valve voltages, and fan configurations for different HVAC systems.

Control Status

Commissioning

Mode for testing equipment wiring and functionality after installation to ensure proper operation.

Troubleshooting

Fault List

A comprehensive list of faults, their probable causes, and recommended solutions for diagnosing issues.

Troubleshooting Details¹ (Part 1 of 2)

Symptoms

Details specific controller symptoms and their probable causes and solutions for effective troubleshooting.

Troubleshooting Details¹ (Part 2 of 2)

Technical Specifications

Johnson Controls TEC3011 Specifications

General IconGeneral
TypeElectronic Temperature Controller
Display TypeLCD
Control OutputSPDT Relay
MountingWall Mount
Enclosure RatingIP30
Operating Temperature0 to 50 °C