EasyManua.ls Logo

Johnson Controls TEC3022 - User Manual

Johnson Controls TEC3022
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series On/Off or Floating Fan
Coil Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostat Controllers are stand-alone and field-selectable
BACnet
®
MS/TP or N2 networked devices. Wireless networked models of the TEC3000 Series
Thermostat Controller are also available. On/Off or Floating Fan Coil and Individual Zone
Thermostat Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV) equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/
TP or N2 communication capability that enables remote monitoring and programming for efficient
space temperature control. The wireless models are compatible with the WNC1800/ZFR182x Pro
Series Wireless Field Bus System that enables communication with a building automation system
(BAS). All models include a USB port configuration that reduces installation time by allowing
simple backup and restore features from a USB drive, which enables rapid cloning of configuration
between like units.
Some models feature built-in occupancy sensing capability. These thermostat controllers maximize
up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels,
during occupied times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and
operation quick and easy. Multiple fan configurations are supported for fan coil equipment types,
as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan
coil units with or without reheat. When no heating is required, the thermostat controller monitors
space humidity and activates dehumidification control as necessary. Heat and/or reheat is used as
required to maintain the space temperature. For optimal dehumidification performance, use a fan
coil unit that has a multi-speed or variable-speed fan (VSF).
Important: The TEC3000 Series Thermostat Controller is intended to provide an input to
equipment under normal operating conditions. Where failure or malfunction of the thermostat
controller could lead to personal injury or property damage to the controlled equipment or
other property, additional precautions must be designed into the control system. Incorporate
and maintain other devices, such as supervisory or alarm systems or safety or limit controls,
intended to warn of or protect against failure or malfunction of the thermostat controller.
TEC3012-1x-xxx, TEC3013-1x-xxx, TEC3310-1x-xxx,
TEC3313-1x-xxx, TEC3612-1x-xxx, TEC3613-1x-xxx
LIT-12013161
2019-08-20

Other manuals for Johnson Controls TEC3022

Questions and Answers

  • D
    Douglas DeanSep 14, 2025
    What does it mean when my Johnson Controls TEC3022 Controller displays an Open Window error?
    • S
      Shannon BryantSep 15, 2025
      If your Johnson Controls Controller displays an 'Open Window' error, it means the switch connected to the BI configured for Open Window is sensing that a window is open, and control has been shut down. Here's how to resolve it: 1. Close the window to resume control. 2. Check the sensor functionality with an ohmmeter, and verify the wiring to the TEC. 3. If problems persist, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • P
    peter64Sep 15, 2025
    Why does my Johnson Controls TEC3022 say 'Cooling Unavailable due to Control Mode' or 'Heating Unavailable due to Control Mode'?
    • C
      Christy HartSep 15, 2025
      If your Johnson Controls Controller displays 'Idle' with a unit status of 'Cooling Unavailable due to Control Mode' (even when above the cooling setpoint) or 'Heating Unavailable due to Control Mode' (even when below the heating setpoint), it indicates that the control mode setting is incorrect. Here’s what you should do: * If the Control Mode is set to 'Cooling Mode' but the controller is requesting heating, change the Control Mode to 'Auto' or 'Heating'. * If the Control Mode is set to 'Heating Mode' but the controller is requesting cooling, change the Control Mode to 'Auto' or 'Cooling'.
  • K
    Kevin MathewsSep 15, 2025
    Why is my Zone Temperature Too Cold according to my Johnson Controls TEC3022?
    • W
      Willie WatkinsSep 15, 2025
      If your Johnson Controls Controller indicates that the zone temperature is too cold, it means the zone temperature has dropped below the configured Zone Temp Low Limit. To address this, verify that the TEC and the RTU heating are both enabled and functioning correctly.
  • C
    courtneyschmittSep 15, 2025
    What to check if Johnson Controls TEC3022 Controller says Zone Temperature Too Hot?
    • M
      Mr. Wyatt OlsonSep 15, 2025
      If your Johnson Controls Controller reports that the zone temperature is too hot, it means the zone temperature has exceeded the configured Zone Temp High Limit. You should verify that the TEC and the RTU cooling are enabled and working properly.
  • A
    akingSep 15, 2025
    What does the Service alarm mean on my Johnson Controls TEC3022 Controller?
    • K
      Katie JohnsonSep 15, 2025
      If your Johnson Controls Controller is showing a 'Service' alarm, it indicates that equipment connected to the BI configured for a Service alarm is triggering the alarm. You should service the equipment following the manufacturer's recommendations.
  • C
    Cindy FlynnSep 16, 2025
    Why does Johnson Controls TEC3022 Controller display 'Cooling Unavailable' or 'Heating Unavailable' when it should be cooling or heating?
    • J
      Jose WestSep 16, 2025
      If your Johnson Controls Controller displays 'Idle' with a unit status of 'Cooling Unavailable' (despite being above the cooling setpoint) or 'Heating Unavailable' (despite being below the heating setpoint), it means the 'Number of Compressors' is set to 'Not Used' while the controller is requesting cooling, or the 'Number of Heating Stages' is set to 'Not Used'. To fix this, adjust the number of compressors and heating stages to match the actual configuration of the unit.
  • E
    Eduardo ConradSep 16, 2025
    How do I fix Touchscreen Unavailable error on Johnson Controls TEC3022 Controller?
    • T
      tinagrossSep 16, 2025
      If your Johnson Controls Controller displays 'Touchscreen Unavailable', it means the touchscreen components have failed to initialize. Here’s how to troubleshoot it: 1. Reboot the controller. 2. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • N
    Nicole HowellSep 16, 2025
    What should I do if my Johnson Controls TEC3022 displays Internal Sensor Fail?
    • C
      Courtney JordanSep 16, 2025
      If your Johnson Controls Controller displays 'Internal Sensor Fail', it means an internal sensor has failed. The suggested solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • C
    Christopher WaltersSep 16, 2025
    What does it mean when the Supply Fan Runtime Limit is Extended on my Johnson Controls Controller?
    • W
      wagnernathanSep 16, 2025
      If your Johnson Controls Controller indicates that the Supply Fan Runtime Limit has been extended, it means the supply fan runtime has exceeded the configured limit. To resolve this: 1. Service the supply fan. 2. Reset the supply fan runtime.
  • R
    Randall AlvarezSep 17, 2025
    How to fix USB Malfunction on Johnson Controls Controller?
    • C
      chelseakimSep 17, 2025
      If you are encountering a 'USB Malfunction' error on your Johnson Controls Controller, it indicates that a USB drive has malfunctioned and drawn more current than allowed. Here's what you can do: 1. Try inserting and using the USB drive again. 2. Try a different USB drive. 3. If the problem continues, order replacement units and return the affected devices to Johnson Controls under the RMA program.

Summary

Applications

Capabilities and Features

Describes networked/wireless models, occupancy sensing, touchscreen UI, fan configs, and dehumidification.

Installation

Installing the Thermostat Controller

Removing and Mounting the Controller

Steps for removing cover and mounting the base.

Wiring

Terminal Identification and Functions

Describes terminal labels and their functions for various models.

Using the USB Port

Firmware Loading and Backup

Steps for updating firmware and backing up settings.

Settings Restoration and Communication Mode

Procedures for restoring settings and configuring network communication.

Installer Configuration Menu

Screen Reset and Unit Type Selection

How to reset screen and choose between 2-pipe, 4-pipe, or VAV configurations.

Heating;Cooling Type and Fan Configuration

Setting control modes and fan parameters.

VSF, Control Mode, and Fan Mode Settings

Configuring VSF, control modes, and fan operation.

Dehumidification Control

Temperature Setpoints

Configuring Occupancy

PID;PRAC+ Automatic Control Tuning

Resetting and Disabling PID Tuning

Procedures to reset and disable PID tuning parameters.

Available Fault Diagnostics

Troubleshooting

Common Sensor and Temperature Faults

Faults and solutions for zone, supply, and outdoor temperature failures.

Other Faults and Solutions

Faults and solutions for internal sensor, dehumidification, service, and calibration issues.

Faults related to Inputs and Control States

Faults and solutions for open window, fan lock, humidity, and controller errors.

Faults related to Hardware and Firmware

Faults and solutions for touchscreen, board mismatch, firmware, USB, and runtime issues.

Troubleshooting HVAC Operation Faults

Symptoms, causes, and solutions for cooling/heating unavailability and cycling.

Troubleshooting Control and Configuration Errors

Issues with firmware upgrades, temperature response, and unoccupied settings.

Troubleshooting Backup and Restore Errors

Issues with settings backup, restore, and USB access.

Troubleshooting Display and Network Issues

Issues with unresponsive touchscreens, hidden icons, and network connectivity.

Technical Specifications

Johnson Controls TEC3022 Specifications

General IconGeneral
ModelTEC3022
Product TypeTemperature Controller
Supply Voltage24 VAC/VDC
Communication ProtocolBACnet MS/TP
Number of Inputs2
Number of Outputs2
Control AlgorithmPID
DisplayLCD
Enclosure RatingIP20
MountingWall Mount
TypeThermostat
Controller TypeDigital
ApplicationHVAC
Input TypeThermistor
Output TypeRelay
Power Supply24 VAC

Related product manuals