EasyManua.ls Logo

Johnson Controls TEC3022 - User Manual

Johnson Controls TEC3022
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series On/Off or Floating Fan
Coil Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostat Controllers are stand-alone and field-selectable
BACnet
®
MS/TP or N2 networked devices. Wireless networked models of the TEC3000 Series
Thermostat Controller are also available. On/Off or Floating Fan Coil and Individual Zone
Thermostat Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV) equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/
TP or N2 communication capability that enables remote monitoring and programming for efficient
space temperature control. The wireless models are compatible with the WNC1800/ZFR182x Pro
Series Wireless Field Bus System that enables communication with a building automation system
(BAS). All models include a USB port configuration that reduces installation time by allowing
simple backup and restore features from a USB drive, which enables rapid cloning of configuration
between like units.
Some models feature built-in occupancy sensing capability. These thermostat controllers maximize
up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels,
during occupied times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and
operation quick and easy. Multiple fan configurations are supported for fan coil equipment types,
as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan
coil units with or without reheat. When no heating is required, the thermostat controller monitors
space humidity and activates dehumidification control as necessary. Heat and/or reheat is used as
required to maintain the space temperature. For optimal dehumidification performance, use a fan
coil unit that has a multi-speed or variable-speed fan (VSF).
Important: The TEC3000 Series Thermostat Controller is intended to provide an input to
equipment under normal operating conditions. Where failure or malfunction of the thermostat
controller could lead to personal injury or property damage to the controlled equipment or
other property, additional precautions must be designed into the control system. Incorporate
and maintain other devices, such as supervisory or alarm systems or safety or limit controls,
intended to warn of or protect against failure or malfunction of the thermostat controller.
TEC3012-1x-xxx, TEC3013-1x-xxx, TEC3310-1x-xxx,
TEC3313-1x-xxx, TEC3612-1x-xxx, TEC3613-1x-xxx
LIT-12013161
2019-08-20

Other manuals for Johnson Controls TEC3022

Questions and Answers

  • C
    craigryanSep 18, 2025
    What to do if Humidity is Unreliable on Johnson Controls TEC3022?
    • A
      Ariel MeyersSep 18, 2025
      If your Johnson Controls Controller shows 'Humidity Unreliable,' it means the zone humidity reading was reliable but has now failed. Here's how to address it: 1. If the source of zone humidity was the onboard sensor, contact Johnson Controls product sales and support. 2. If the source of zone humidity was a BAS, check the BAS to ensure it's still online and providing the TEC with the humidity reading. If removing the BAS mapping was intentional, reset sensors through the menu.
  • D
    Denise JohnsonSep 18, 2025
    What does Supply Fan Fault mean on my Johnson Controls TEC3022 Controller?
    • R
      Ryan CantuSep 18, 2025
      If your Johnson Controls Controller displays a 'Supply Fan Fault', it means the supply fan status configured for either BI1 or BI2 hasn't been proven within the configured fan alarm delay. To resolve this: 1. Verify that the supply fan is operating when turned on. 2. Verify that the supply fan status wiring is connected correctly.
  • R
    Raymond HarrisonSep 18, 2025
    How do I resolve a Firmware Mismatch error on my Johnson Controls TEC3022 Controller?
    • G
      graveskatherineSep 18, 2025
      If you encounter a 'Firmware Mismatch' error on your Johnson Controls Controller, it indicates that a previous upgrade or downgrade process did not complete successfully. Here’s how to address it: * If the previous upgrade didn't complete, upgrade the TEC3000 to the latest released version and then upgrade it to the current version again. * If a previous downgrade didn't complete because the previous version is no longer supported, reboot the TEC3000 to clear the fault.
  • J
    Jeffery HallSep 18, 2025
    What should I do if my Johnson Controls Controller displays Calibration Corrupt?
    • J
      Joanna SimonSep 18, 2025
      If your Johnson Controls Controller displays 'Calibration Corrupt', it means that the factory calibration data is lost or not installed. The suggested solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • T
    Tiffany RogersSep 18, 2025
    What does Board Mismatch mean on Johnson Controls TEC3022 Controller?
    • N
      Nicole PinedaSep 18, 2025
      If your Johnson Controls Controller displays 'Board Mismatch', it means the baseboard and CPU board are paired incorrectly, with an error message indicating the model numbers. To fix this, match the baseboard to its corresponding CPU board. Consult Table 2 for information on ensuring the correct pairing.
  • C
    Craig WrightSep 18, 2025
    Why is Heating Ineffective on my Johnson Controls Controller?
    • J
      Julia SampsonSep 18, 2025
      If your Johnson Controls Controller indicates 'Heating Ineffective,' it means the supply air temperature hasn't increased above the configured Supply Air Temperature Alarm Offset, even though heating has been active for at least the Supply Air Temperature Alarm Delay. To resolve this, verify that the heating elements on the rooftop are functioning properly.
  • T
    Thomas MaciasSep 18, 2025
    Why is Cooling Ineffective on my Johnson Controls TEC3022 Controller?
    • S
      sjonesSep 18, 2025
      If your Johnson Controls Controller reports 'Cooling Ineffective', it means that the supply air temperature hasn't decreased below the configured Supply Air Temperature Alarm Offset while cooling has been active for at least the Supply Air Temperature Alarm Delay. To fix this, verify that the cooling elements on the rooftop are functioning properly.
  • M
    Manuel SmithSep 19, 2025
    What should I do if my Johnson Controls Controller displays Zone Temp Unreliable?
    • A
      Annette RileySep 19, 2025
      If your Johnson Controls Controller displays 'Zone Temp Unreliable,' it means all sources of zone temperature, including the onboard sensor, are unreliable. The suggested solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • M
    Monica BryantSep 22, 2025
    Why does my Johnson Controls heat pump heat when it should cool, and cool when it should heat?
    • R
      Ryan DelgadoSep 22, 2025
      If your heat pump heats when it should be cooling, and cools when it should be heating, it indicates that the reversing valve polarity is set incorrectly. To fix this, consult the equipment documentation to verify the correct reversing valve polarity, and then adjust the Reversing Valve Polarity menu option accordingly.
  • C
    Connie BlakeSep 22, 2025
    What does Partial Restore Complete mean when restoring settings on my Johnson Controls Controller?
    • M
      melissa85Sep 22, 2025
      If 'Partial Restore Complete' is displayed when trying to restore settings from a backup file, it means that not all items in the backup file have been restored. This can occur if a value is out of the acceptable range or if there are inconsistencies in the reliability of a setting. To resolve this: 1. Create a backup file on a USB drive for the TEC that is showing the issue. 2. Edit the backup file on a computer to reflect the preferred settings. 3. Verify that the modified values are within the minimum and maximum range in the backup file. 4. Restore the settings from the newly edited backup file on the TEC.

Summary

Applications

Capabilities and Features

Describes networked/wireless models, occupancy sensing, touchscreen UI, fan configs, and dehumidification.

Installation

Installing the Thermostat Controller

Removing and Mounting the Controller

Steps for removing cover and mounting the base.

Wiring

Terminal Identification and Functions

Describes terminal labels and their functions for various models.

Using the USB Port

Firmware Loading and Backup

Steps for updating firmware and backing up settings.

Settings Restoration and Communication Mode

Procedures for restoring settings and configuring network communication.

Installer Configuration Menu

Screen Reset and Unit Type Selection

How to reset screen and choose between 2-pipe, 4-pipe, or VAV configurations.

Heating;Cooling Type and Fan Configuration

Setting control modes and fan parameters.

VSF, Control Mode, and Fan Mode Settings

Configuring VSF, control modes, and fan operation.

Dehumidification Control

Temperature Setpoints

Configuring Occupancy

PID;PRAC+ Automatic Control Tuning

Resetting and Disabling PID Tuning

Procedures to reset and disable PID tuning parameters.

Available Fault Diagnostics

Troubleshooting

Common Sensor and Temperature Faults

Faults and solutions for zone, supply, and outdoor temperature failures.

Other Faults and Solutions

Faults and solutions for internal sensor, dehumidification, service, and calibration issues.

Faults related to Inputs and Control States

Faults and solutions for open window, fan lock, humidity, and controller errors.

Faults related to Hardware and Firmware

Faults and solutions for touchscreen, board mismatch, firmware, USB, and runtime issues.

Troubleshooting HVAC Operation Faults

Symptoms, causes, and solutions for cooling/heating unavailability and cycling.

Troubleshooting Control and Configuration Errors

Issues with firmware upgrades, temperature response, and unoccupied settings.

Troubleshooting Backup and Restore Errors

Issues with settings backup, restore, and USB access.

Troubleshooting Display and Network Issues

Issues with unresponsive touchscreens, hidden icons, and network connectivity.

Technical Specifications

Johnson Controls TEC3022 Specifications

General IconGeneral
ModelTEC3022
Product TypeTemperature Controller
Supply Voltage24 VAC/VDC
Communication ProtocolBACnet MS/TP
Number of Inputs2
Number of Outputs2
Control AlgorithmPID
DisplayLCD
Enclosure RatingIP20
MountingWall Mount
TypeThermostat
Controller TypeDigital
ApplicationHVAC
Input TypeThermistor
Output TypeRelay
Power Supply24 VAC

Related product manuals