EasyManua.ls Logo

Johnson Controls TEC3022 - User Manual

Johnson Controls TEC3022
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series On/Off or Floating Fan
Coil Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostat Controllers are stand-alone and field-selectable
BACnet
®
MS/TP or N2 networked devices. Wireless networked models of the TEC3000 Series
Thermostat Controller are also available. On/Off or Floating Fan Coil and Individual Zone
Thermostat Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV) equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/
TP or N2 communication capability that enables remote monitoring and programming for efficient
space temperature control. The wireless models are compatible with the WNC1800/ZFR182x Pro
Series Wireless Field Bus System that enables communication with a building automation system
(BAS). All models include a USB port configuration that reduces installation time by allowing
simple backup and restore features from a USB drive, which enables rapid cloning of configuration
between like units.
Some models feature built-in occupancy sensing capability. These thermostat controllers maximize
up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels,
during occupied times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and
operation quick and easy. Multiple fan configurations are supported for fan coil equipment types,
as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan
coil units with or without reheat. When no heating is required, the thermostat controller monitors
space humidity and activates dehumidification control as necessary. Heat and/or reheat is used as
required to maintain the space temperature. For optimal dehumidification performance, use a fan
coil unit that has a multi-speed or variable-speed fan (VSF).
Important: The TEC3000 Series Thermostat Controller is intended to provide an input to
equipment under normal operating conditions. Where failure or malfunction of the thermostat
controller could lead to personal injury or property damage to the controlled equipment or
other property, additional precautions must be designed into the control system. Incorporate
and maintain other devices, such as supervisory or alarm systems or safety or limit controls,
intended to warn of or protect against failure or malfunction of the thermostat controller.
TEC3012-1x-xxx, TEC3013-1x-xxx, TEC3310-1x-xxx,
TEC3313-1x-xxx, TEC3612-1x-xxx, TEC3613-1x-xxx
LIT-12013161
2019-08-20

Other manuals for Johnson Controls TEC3022

Questions and Answers

  • K
    Karen ClarkSep 22, 2025
    Why does my Johnson Controls staged equipment shut off prematurely when the PID is running?
    • C
      Crystal LopezSep 22, 2025
      If your staged equipment shuts off above the cooling setpoint or below the heating setpoint when the PID is running on the TEC, it is expected behavior. The PID control algorithm minimizes overshoot and energy usage, which may cause the equipment to cycle before reaching the setpoint.
  • S
    Sarah BenitezSep 22, 2025
    Why is the temperature displayed on my Johnson Controls TEC lower than the actual room temperature?
    • J
      John CollinsSep 22, 2025
      If the temperature displayed on your TEC is lower than the actual room temperature, it could be due to: * Cold air drafts entering the back of the TEC. Seal any holes behind the TEC to reduce drafts. * Air being forced through the TEC from a nearby vent. Move the location of the TEC or change the venting to prevent air from being forced through the TEC.
  • S
    Sean WilliamsSep 22, 2025
    What does Supervisory Status = Offline mean on my Johnson Controls TEC3022 Controller?
    • M
      mullinsjulieSep 22, 2025
      If your Johnson Controls Controller displays 'Supervisory Status = Offline', it indicates that the supervisory controller isn't communicating with the TEC, the TEC isn't mapped to a JCI Supervisory System, or the WNC Gateway isn't communicating with the TEC. To resolve this: 1. Map the TEC into a JCI Supervisory system. 2. Verify that the PAN’s WNC Gateway is online. 3. Add ZFR Pro Routers/Repeaters into the wireless system.
  • S
    Samantha KruegerSep 23, 2025
    Why are some icons hidden on my Johnson Controls TEC3022 Controller?
    • N
      Nicole ParkerSep 23, 2025
      If some icons are hidden on your Johnson Controls Controller, it's because lockout levels are in use or the icons are hidden due to the display settings. See Table 5 for lockout levels and access details.
  • B
    Brandon WilsonSep 23, 2025
    What does Controller Fault mean on Johnson Controls Controller?
    • A
      Amanda RodriguezSep 23, 2025
      If your Johnson Controls Controller displays 'Controller Fault', it means the controller has detected an internal fault that it cannot recover from, or an unknown error has prevented the controller from turning on. The suggested solution is to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • X
    xtylerSep 23, 2025
    What to do if Johnson Controls TEC3022 provides an error when trying to upgrade firmware?
    • R
      Ronald PowellSep 23, 2025
      If your Johnson Controls Controller provides an error when trying to upgrade the firmware, it means the firmware on the USB drive is below the minimum required version (Error code 1025). Please use firmware version 2.0.2.xxxx or higher. A reboot is required to clear the Firmware Mismatch fault that occurs.
  • D
    Darrell TorresSep 23, 2025
    Why is my Johnson Controls TEC3022 unable to access a USB drive?
    • R
      Richard RaySep 23, 2025
      If your Johnson Controls Controller can't access a USB drive, it could be due to a couple of reasons: * The drive is formatted as NTFS or another unsupported format. The TEC supports FAT16 and FAT32 formats only. Reformat the USB drive, or try a different USB drive with a supported format. * The USB drive is defective. Try a different USB drive.
  • D
    Danielle LeeSep 23, 2025
    Why does my Johnson Controls staged equipment cycle too rapidly or slowly when the PID is running?
    • S
      smcmillanSep 23, 2025
      If your staged equipment cycles too rapidly or too slowly when the PID is running on the TEC, it's likely due to the control band around the setpoint being incorrectly set for the equipment, zone, or user preference. To adjust this: 1. Verify that the equipment's minimum on/off times are set correctly. 2. If the default deadband doesn't provide the desired temperature control, set 'Temp Control Setup' to 'Deadband Override' and adjust the 'Deadband' parameter to the desired value.
  • P
    Peter GrimesSep 23, 2025
    What should I do if my Johnson Controls TEC3022 Controller displays Board Mismatch?
    • A
      Annette WardSep 23, 2025
      If your Johnson Controls Controller displays 'Board Mismatch', it could be due to the following reasons: * The I/O board that the display board is currently attached to does not match the one that initially shipped with the display board. Attach the display board to the correct I/O board. * A hardware failure is causing the two boards to incorrectly identify themselves. Order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • T
    Todd CrossSep 23, 2025
    What should I do if my Johnson Controls TEC3022 Controller displays Controller Fault?
    • J
      John RodriguezSep 23, 2025
      If your Johnson Controls Controller displays 'Controller Fault', it means an internal fault was detected and the controller was unable to recover. Order replacement units and return the affected devices to Johnson Controls under the RMA program.

Summary

Applications

Capabilities and Features

Describes networked/wireless models, occupancy sensing, touchscreen UI, fan configs, and dehumidification.

Installation

Installing the Thermostat Controller

Removing and Mounting the Controller

Steps for removing cover and mounting the base.

Wiring

Terminal Identification and Functions

Describes terminal labels and their functions for various models.

Using the USB Port

Firmware Loading and Backup

Steps for updating firmware and backing up settings.

Settings Restoration and Communication Mode

Procedures for restoring settings and configuring network communication.

Installer Configuration Menu

Screen Reset and Unit Type Selection

How to reset screen and choose between 2-pipe, 4-pipe, or VAV configurations.

Heating;Cooling Type and Fan Configuration

Setting control modes and fan parameters.

VSF, Control Mode, and Fan Mode Settings

Configuring VSF, control modes, and fan operation.

Dehumidification Control

Temperature Setpoints

Configuring Occupancy

PID;PRAC+ Automatic Control Tuning

Resetting and Disabling PID Tuning

Procedures to reset and disable PID tuning parameters.

Available Fault Diagnostics

Troubleshooting

Common Sensor and Temperature Faults

Faults and solutions for zone, supply, and outdoor temperature failures.

Other Faults and Solutions

Faults and solutions for internal sensor, dehumidification, service, and calibration issues.

Faults related to Inputs and Control States

Faults and solutions for open window, fan lock, humidity, and controller errors.

Faults related to Hardware and Firmware

Faults and solutions for touchscreen, board mismatch, firmware, USB, and runtime issues.

Troubleshooting HVAC Operation Faults

Symptoms, causes, and solutions for cooling/heating unavailability and cycling.

Troubleshooting Control and Configuration Errors

Issues with firmware upgrades, temperature response, and unoccupied settings.

Troubleshooting Backup and Restore Errors

Issues with settings backup, restore, and USB access.

Troubleshooting Display and Network Issues

Issues with unresponsive touchscreens, hidden icons, and network connectivity.

Technical Specifications

Johnson Controls TEC3022 Specifications

General IconGeneral
ModelTEC3022
Product TypeTemperature Controller
Supply Voltage24 VAC/VDC
Communication ProtocolBACnet MS/TP
Number of Inputs2
Number of Outputs2
Control AlgorithmPID
DisplayLCD
Enclosure RatingIP20
MountingWall Mount
TypeThermostat
Controller TypeDigital
ApplicationHVAC
Input TypeThermistor
Output TypeRelay
Power Supply24 VAC

Related product manuals