EasyManua.ls Logo

Johnson Controls TEC3030 - User Manual

Johnson Controls TEC3030
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series Networked and Wireless
Single- or Two-stage Economizer Thermostat
Controllers Quick Start Guide
North American emissions
compliance
United States
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to Part15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference ina
residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if notinstalled
and used in accordance with the instructions, may cause
harmful interference to radio communications.However,
there is no guarantee that interference will not occur
in a particular installation. If this equipment doescause
harmful interference to radio or television reception,
which can be determined by turning the equipment
offand on, the user is encouraged to try to correct the
interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV
technician for help.
Canada
This Class (B) digital apparatus meets all the requirements
of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes
les exigences du Réglement sur le matériel brouilleurdu
Canada.
Installation
Parts included
One TEC3000 Series Thermostat Controller with integral
mounting base
One installation instructions sheet
Location considerations
For networked models, locate the TEC3000 Series
Thermostat Controller:
On a partitioning wall, approximately 5 ft (1.5 m) above
the floor in a location of average temperature, to allow
for vertical air circulation to the TEC
Away from direct sunlight, radiant heat, outside walls,
outside doors, air discharge grills, stairwells, and from
behind doors
Away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or sources
of electrical interference
In a clear path between the integrated passive infrared
(PIR) occupancy sensor (if equipped) and the space it
monitors
For wireless models, also locate the thermostat controller:
Outside of a recessed area, metal enclosure, or shelving
unit
On the same building level as the other wireless devices
on the same personal area network (PAN)
At least 2 in. (51 mm) away from any metal obstruction
In the direct line of sight to other wireless devices on
the same PAN. Signal transmission is best if the path
between the TEC3000 and other wireless devices is
direct as possible. Line of sight is desirable but not
required. See Table 1 and Table 2 for the recommended
and maximum distances.
Away from metal and large solid obstructions, that
includes equipment rooms and elevator shafts and
concrete or brick walls, between the TEC3000 and
the ZFR182x or ZFR183x Router/Repeater or ZFR Pro
Coordinator Radio
Within range of two or more wireless devices on the
same PAN. Redundancy in the layout provides the best
reliability in wireless installations
At least 20 ft (6 m) from a microwave oven
For integrated PIR models, make sure that the thermostat
controller is located centrally, where occupant movement
is frequent. Ensure that the unit is not blocked by a plastic
tamper resistant enclosure (such as the GRD10A-608). The
plastic enclosure blocks the occupancy sensing capability.
The use of insulating foam pads is necessary for
installations where wiring passes through the wall to the
thermostat.
For wireless models, the effective transmission range and
distance for indoor applications vary because of wireless
signal absorption and reflection due to metal obstructions,
walls or floors, and furniture that is found in building
interiors.
Note: Allow for sufficient clearance to insert a USB
drive into the USB port
Important: Only connect memory devices to the USB
port. Do not use it for charging external devices.
*241135300036E*
Part No. 24-11353-00036 Rev. E
2020-12-15
(barcode for factory use only)
TEC3330-1x-xxx, TEC3331-1x-xxx, TEC3630-1x-xxx,
TEC3631-1x-xxx, TEC3030-1x-xxx, TEC3031-1x-xxx,
TEC313x-14-xxx

Other manuals for Johnson Controls TEC3030

Questions and Answers

  • A
    Angela BeltranSep 12, 2025
    What to do if I see Remote Zone Temp Fail on Johnson Controls Controller?
    • S
      Sarah ChandlerSep 12, 2025
      The 'Remote Zone Temp Fail' error on your Johnson Controls Controller indicates that the external zone temperature sensor is either disconnected or has failed. To resolve this: 1. Check the wiring of the sensor to ensure it is properly connected. 2. If the sensor was intentionally disconnected, reset the sensors through the menu. 3. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • M
    matthew34Sep 12, 2025
    How do I troubleshoot a Supply Temp Fail error on my Johnson Controls TEC3030 Controller?
    • W
      wrightgeorgeSep 12, 2025
      A 'Supply Temp Fail' error on your Johnson Controls Controller means that the external supply temperature sensor is either disconnected or has failed. Here’s how you can troubleshoot it: 1. Check the wiring of the sensor to ensure it is properly connected. 2. If the sensor was intentionally disconnected, reset the sensors through the menu. 3. If the problem continues, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • N
    Nicholas MortonSep 12, 2025
    Why is the Econ Unavailable on my Johnson Controls Controller?
    • M
      Melissa CochranSep 12, 2025
      If your Johnson Controls Controller displays 'Econ Unavailable', it means the outdoor air temperature sensor is either not installed, has failed, or has been disconnected, preventing the controller from managing the economizer. To fix this, follow the same steps as for an Outdoor Temp Fail alarm: * Check the wiring of the sensor. * If intentionally disconnected, reset sensors through the menu. * If problems persist, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • M
    Mr. Victor OwensSep 13, 2025
    Why does my Johnson Controls Controller display 'Cooling Unavailable due to OA Temp' or 'Heating Unavailable due to OA Temp'?
    • T
      Tiffany JonesSep 13, 2025
      If your Johnson Controls Controller displays 'Idle' with a unit status of 'Cooling Unavailable due to OA Temp' (despite being above the cooling setpoint) or 'Heating Unavailable due to OA Temp' (despite being below the heating setpoint), it means the outdoor air temperature is either too warm for heating or too cold for cooling. To resolve this: 1. Adjust the Cooling and Heating Lockout Setpoints if they are inadequate. 2. Alternatively, wait for the outdoor conditions to become more suitable for heating or cooling.
  • J
    Jill VaughanSep 13, 2025
    What should I do if my Johnson Controls TEC3030 shows a Dirty Filter alarm?
    • M
      Michael KingSep 13, 2025
      If your Johnson Controls Controller is showing a 'Dirty Filter' alarm, it means that the equipment connected to the BI configured for this alarm is triggering it. The solution is to replace the filter in the equipment, following the instructions provided by the manufacturer.
  • P
    paulguzmanSep 13, 2025
    How do I fix a Fan Lock error on my Johnson Controls TEC3030?
    • J
      Joseph SmithSep 13, 2025
      If you're getting a 'Fan Lock' error on your Johnson Controls Controller, it means the switch connected to the BI configured for Fan Lock didn't sense airflow within 10 seconds of starting the fan, and control has been shut down. Here’s how to address it: 1. Check the equipment to ensure the fan is working correctly. 2. Use an ohmmeter to check the sensor's functionality and verify the wiring to the TEC. 3. Reset the fault by going to the menu, selecting 'Fault Status,' and then selecting 'Fan Lock'. 4. If the problem persists, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • M
    Michael EdwardsSep 13, 2025
    What does it mean when my Johnson Controls Controller displays an Open Window error?
    • R
      Rachel GonzalezSep 13, 2025
      If your Johnson Controls Controller displays an 'Open Window' error, it means the switch connected to the BI configured for Open Window is sensing that a window is open, and control has been shut down. Here's how to resolve it: 1. Close the window to resume control. 2. Check the sensor functionality with an ohmmeter, and verify the wiring to the TEC. 3. If problems persist, order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • J
    jameslarsonSep 14, 2025
    Why does my Johnson Controls Controller say 'Cooling Unavailable due to Control Mode' or 'Heating Unavailable due to Control Mode'?
    • C
      Crystal WilliamsSep 14, 2025
      If your Johnson Controls Controller displays 'Idle' with a unit status of 'Cooling Unavailable due to Control Mode' (even when above the cooling setpoint) or 'Heating Unavailable due to Control Mode' (even when below the heating setpoint), it indicates that the control mode setting is incorrect. Here’s what you should do: * If the Control Mode is set to 'Cooling Mode' but the controller is requesting heating, change the Control Mode to 'Auto' or 'Heating'. * If the Control Mode is set to 'Heating Mode' but the controller is requesting cooling, change the Control Mode to 'Auto' or 'Cooling'.
  • E
    Edward SmithSep 14, 2025
    Why is my Zone Temperature Too Cold according to my Johnson Controls Controller?
    • B
      bradshawcharlesSep 14, 2025
      If your Johnson Controls Controller indicates that the zone temperature is too cold, it means the zone temperature has dropped below the configured Zone Temp Low Limit. To address this, verify that the TEC and the RTU heating are both enabled and functioning correctly.
  • D
    Danny KelleySep 14, 2025
    What to check if Johnson Controls Controller says Zone Temperature Too Hot?
    • E
      Ernest Neal MDSep 14, 2025
      If your Johnson Controls Controller reports that the zone temperature is too hot, it means the zone temperature has exceeded the configured Zone Temp High Limit. You should verify that the TEC and the RTU cooling are enabled and working properly.

Summary

North American Emissions Compliance

United States FCC Compliance

Details FCC Part 15 compliance for Class B digital devices in residential settings.

Canada Interference Regulations

States compliance with Canadian Interference-Causing Equipment Regulations.

Installation and Wiring

Installation Parts and Location

Lists included parts and provides guidance on optimal controller placement.

Mounting the Thermostat Controller

Step-by-step instructions for physically installing the thermostat.

Wiring Diagrams

Visual guides for connecting the thermostat to HVAC systems.

System Setup and Configuration

Home Screen and Display Customization

Personalizing the thermostat's home screen appearance and display options.

Touchscreen Interface and Icon Guide

Explains the meaning and function of all touchscreen icons.

User Access and USB Port Operations

Managing user lockout levels and utilizing the USB port for firmware.

Installer Configuration Menu

Accessing and performing initial controller setup tasks.

System Mode and Economizer Settings

Configuring HVAC modes, economizer availability, and related parameters.

Control, Fan, and Setpoint Configuration

Adjusting control modes, fan operation, and temperature setpoints.

Scheduling and Occupancy Management

Setting occupancy schedules and managing occupancy modes.

Advanced Control Features

Configuring dehumidification, optimal start, and motion sensing.

Auxiliary Output and Fan Circulation Control

Configuring auxiliary outputs and scheduled fan circulation.

Johnson Controls TEC3030 Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3030
CategoryController
LanguageEnglish

Related product manuals