JOHNSON CONTROLS
98
FORM 150.72-NM1 (1020)
Technical Data
DIMENSIONS – YLAA0091 TO 0120 (ENGLISH)
Water Connection Sizes are shown
in the Physical Data Table
F
W
P
D
C1
C2
R2 R1
(TYP)
H
L
YLAA Model
L
(length)
W
(width)
H
(height)
F P D C1 C2 R4 R3 R2 R1
YLAA0091HE 143.5 88.3 94.2 88.5 42.8 15 18.6 85 NA NA 96 2.3
YLAA0101HE 143.5 88.3 94.2 88.5 42.8 15 18.6 85 NA NA 96 23
YLAA0115SE 143.5 88.3 94.2 88.5 42.8 15 18.6 85 NA NA 96 23
YLAA0120SE 143.5 88.3 94.2 88.5 42.8 17.3 22 102 NA NA 96 23
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow pat-
terns and possible diminished performance. Johnson Controls unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no higher
than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0''; top – no
obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
SIX FAN UNITS