INSTALLATIONS 
3-17
Caution of SENSOR (38.4kbps) connection (Setting for ter
minator) 
The location of the terminator is described on the previous page. 
Pin No. 1 2 3 4
Function Terminator 
for SENSOR1
Terminator 
for SENSOR2
Terminator 
for SENSOR3
Non 
connection 
ON 
100Ω 100Ω 100Ω 
--- 
OFF Open Open Open ---
(D) NETWORK 
Connect the LAN connector to the RMS (Remote Maintenance System) or PC for software 
upgrading.  
The LAN port can connect to IEC61162-450 compliant equipment. 
No. Name  No. Name 
1 TX+  5 NC 
2 TX-  6 RX- 
3 RX+  7 NC 
4 NC  8 NC 
RS-422 
NCM-983 AIS Controller 
100Ω 
Shielding braided wires 
100Ω
SENSOR 
     out
ut 
Other system 
GND-ISO 
DIP Switch
When the line is terminated with 100-ohm 
resistor by other system, set the DIP 
Switch to the off position.
 
Dip switch function  (Initial setting is all ON.)