Operating Instructions Powador 1501xi/2501xi*/3501xi/4501xi/5001xi** Page 15
Fault Cause of fault
Troubleshooting/Explanation
The inverter's display
shows the error message
“Failure PV overvoltage”.
The solar voltage on the
solar generator has risen
to above 500 V.
The inverter is designed for a maximum input voltage of 500 V
from the solar generator.
An incorrect module arrangement or the incorrect dimensioning
of the solar installation can result in this voltage being exceeded.
To protect the inverter, it does not begin feeding into the grid
until the input voltage once again falls below 500 V.
The inverter is active but
does not feed into the
grid – the display shows:
Start at 125 V meas. xxx
V (measured voltage is
greater than 125 V)
The inverter has inter-
rupted the grid feed due
to a fault.
After an interruption to the grid feed due to a fault (line failure,
overtemperature, overload, etc.), the inverter waits a country-
specifi c time period (see Installation Instructions, section 4,
Technical Data) before switching back over to grid feed mode.
With faulty grids, interruptions can occur during the day. Notify
your solar installer if the inverter shuts down regularly over a
period of several weeks (more than 10 times per day with error
messages).
The inverter stops
supplying power to
the grid shortly after
being switched on, even
though there is suffi cient
sunlight.
Faulty grid separation relay
in the inverter.
Although there is suf cient sunlight, the inverter feeds into the
grid only for a few seconds before switching off again. During
the short grid feed period, the inverter shows that the power
being fed into the grid is between 0 and 5 W. If the inverter is
defi nitely receiving suffi cient generator power, the grid separa-
tion relay is presumably faulty, thus preventing the inverter from
connecting.
Noise emission from the
inverter.
Particular ambient condi-
tions.
When there are certain ambient conditions, the units may emit
audible noises. The following causes may be determining factors
in this regard:
Line interference or line failure caused by particular loads
(motors, machines, etc.) which are either connected to
the same point on the grid or located in the vicinity of the
inverter.
In cases of dynamic weather conditions (frequent switching
between sunny and cloudy conditions) or strong solar insola-
tion, a light hum may be audible due to the high output.
With particular grid conditions, resonances may form between
the unit’s input fi lter and the grid, which may be audible even
when the inverter is switched off.
People with very sensitive hearing (particularly children) may be
able to hear the high-frequency hum caused by the inverter’s
operating frequency of approx. 18 kHz.
Such noise emissions do not affect the operation of the inverter.
Nor can they lead to loss of effi ciency, failure, damage or to a
shortening of the units service life.
Table 6.1: Troubleshooting
If the measures described in this guide do not assist in clearing the fault, please notify your installer.
In order for our factory customer service department to respond in an appropriate and expeditious manner, some details are impera-
tive:
Details pertaining to the inverter
The units serial number
Model
A short description of the fault
Is the error or fault reproducible? If yes, how?
Does the error or fault occur sporadically?
Describe the prevailing insolation conditions when the
fault occurred?
Time of day
Details pertaining to the photovoltaic module
Module type, manufacturer (if available, also send the
data sheet)
The number of modules in series
The number of strings
Generator power
Section 6 · Troubleshooting

Table of Contents

Other manuals for Kaco Powador xi Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kaco Powador xi Series and is the answer not in the manual?

Kaco Powador xi Series Specifications

General IconGeneral
BrandKaco
ModelPowador xi Series
CategoryInverter
LanguageEnglish

Related product manuals