KaCool D 02.02.201722
Design and Function
Accessories
Valve Model
2/4
pipe
system
KVS DP max Connection
Cooling
element
Heating
element
Cooling
element
Heating
element
Cooling
element
Heating
element
[m³
/
h] [kPa] [inch]
2-way
valve
1 – 3
2-Pipe 2,8 50 3 / 4"
4-Pipe 2,8 2,8 50 50 3 / 4" 3 / 4"
4 – 6
2-Pipe 5,2 60 1"
4-Pipe 4,5 2,5 60 50 1" 3 / 4"
3-way
valve
1 – 3
2-Pipe 2,5 50 3 / 4"
4-Pipe 5,2 2,8 50 50 3 / 4" 3 / 4"
4 – 6
2-Pipe 4,5 50 1"
4-Pipe 4,5 2,5 50 50 1" 3 / 4"
Valve kit
Thermoelectric actuator (included in valve kit)
Thermoelectric actuator Voltage
Current consumption
(Start) Power consumption
Protection
class
Direction of
operation
[V] [A] [W]
Standard drive
230 0,25 2,5 IP 43
Without current
Closed
Suitable for KaControl
24 0,35 2,5 IP 43