KaCool D 02.02.201754
Maintenance
Maintenance schedule
8.2 Maintenance Schedule
The following sections describe maintenance work that is
required to ensure the optimum and trouble-free operation of
the unit. If increased wear is identi ed during regular checks,
adjust the required maintenance intervals on the basis of the
actual signs of wear. Contact the manufacturer if you have any
questions about maintenance work and intervals (
Chapter 1.4
"Customer Service" on page 6).
Interval Maintenance work Personnel
As required Operating unit display - rstly, observe the separate operating
unit instructions
Caretaker/user
Regular visual inspection of xings and for damage Caretaker/user
Quarterly Visual inspection of lter, replace or clean if necessary
(
Chapter 8.3.1 "Replacing the lter" on page 56)
Caretaker/user
Every six
months
Clean the inside of the unit
(
Chapter 8.3.2 "Cleaning the unit" on page 57)
Caretaker/user
Every six
months
Check water-side connections, valves, screw connections
( Chapter 8.3.2 "Cleaning the unit" on page 57)
Caretaker/user
Every six
months
Vent the heat exchanger
( Chapter 8.3.2 "Cleaning the unit" on page 57)
Caretaker/user
Every six
months
Check electrical connections
(
Chapter 8.3.2 "Cleaning the unit" on page 57)
Caretaker/user
Every six
months
Clean the air discharge grille, remove deposits from the air ow
( Chapter 8.3.2 "Cleaning the unit" on page 57)
Caretaker/user
Every six
months
Check the antifreeze (if used)
(
Chapter 8.3.2 "Cleaning the unit" on page 57)
Caretaker/user
Every six
months
Maintenance of the condensation pump
( Chapter 8.3.2 "Cleaning the unit" on page 57)
Caretaker/user