Page 19
→
→
Pressure at start of tightness test.
→
Real time pressure reading.
→
Tightness default time is 2 minutes. Can be
changed via “Menu”.
When complete the display will show:
→
The tightness test is automatically stored in
the memory.
→
Pressure at start of stabilisation test.
→
Pressure at end of stabilisation test.
→
Pressure at start of tightness test
→
Pressure at end of tightness test
→
Press to print the complete test.
Viewing / printing a logged Let-by and Tightness test
Select MENU / REPORT / TIGHTNESS / VIEW
Use or to select the log number to be printed.
Press / to print the test, (or send to PC via optional Wireless module).
Note: The analyser’s memory can store up to 20 tightness tests. Tightness tests
are logged automatically therefore the tightness section of the memory will
be full after the 20
th
tightness test is complete. Before the 21
st
tightness test
can be performed the tightness section of the memory must be cleared. To
do this select MENU / REPORT / TIGHTNESS / DEL ALL / YES then press
.