13
Error/Message Alt. /
(NUM)
Description Cause/Solution/Troubleshoot
Error Motor
Protection
EOH2
(30)
Electronic
Motor Overload
protection was
activated
Current can be monitored in CP30. Possible causes:
Incorrect motor data
Incorrect encoder data (closed loop only)
Torque boost too high or too low
High mechanical load/issues (friction)
Check:
CP12 Electronic Motor Overload Protection Current
(should match motor nameplate)
Motor Data
CP20 Encoder pulse number
CP21 Swap Encoder Channels
Mechanical load/issues (friction)
Error Overload EOL
(16)
Time dependant
overload. Error
cannot be reset
until display
shows E.nOL
Current can be monitored in CP30. Possible causes:
Excessive current
Incorrect motor data
Incorrect encoder data (closed loop only)
High mechanical load/issues (friction
Torque boost too high or too low (low speed)
Check:
Motor data
CP20 Encoder pulse number
CP21 Swap Encoder Channels
Mechanical load/issues (friction)

Other manuals for KEB ACOMBIVERT F5 X3A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB ACOMBIVERT F5 X3A and is the answer not in the manual?

KEB ACOMBIVERT F5 X3A Specifications

General IconGeneral
BrandKEB
ModelACOMBIVERT F5 X3A
CategoryDC Drives
LanguageEnglish

Related product manuals