Level Crawl Speed
DC-Voltage Circuit Control
Unit: meter per second
Value range: 0,000...0,300 m/s
Factory setting: 0,250 m/s
Adjusted value: dependent on the running time of the door
and speed
Unit: Volt
Value range: 0...800 V
Factory setting: 0 V
Monitors the dc-bus-voltage. If the level is exceeded, the output
X3.22 = high, hysteresis 6%.
„E.dOH“ Delay
Unit: seconds
Value range: 0...3600 s
Factory setting: 300 s
After the delay time has run out, the inverter stops with the message
„E-dOH“ (Error, motor, overheating). The malfunction can be reset,
when the motor has cooled down and the frequency inverter shows
the display „E.nOH“ (Error, no overheating). If the motor cools down
before the delay time runs out, no fault indication is triggered.
For LF.65 = 0 (off) applies: Stop the inverter after the control
release is removed.
8. Parameter Description
Level Overspeed
Unit: meter per second
Value range: 0.000...18,000 m/s
Factory setting: 1,500 m/s
Adjusted value: approx. 1,1 x LF.42
Deceleration Check
Unit: meter per second
Value range: 0,000...15,000 m/s
Factory setting: 1,300 m/s
Adjusted value: approx. 0,95 x LF.42
Controls whether the drive decelerates during shortened overtravel.