8. Parameter Description
2b) switching velocity < ogive speed V
S
, because a
complete s-curve is not possible.
t
delay point
V
V
N
V
E
ogive-status
V
S
The inverter identify that the changeover speed is too high,the ogive
status will be set at 4 and than a ogive drive will be executed. The
drive comfort is not very good.
The ogive status is set at 4, when the ogive drive has finished. Only
when the braking distance or the hight of the floor are adjusted new,
the ogive status will be set at 0.
Measurements:
Distance from the delay point to the levelling signal
Unit: meter
Value range: 0,000 … 5,000 m
Factory setting: 0,000 m
Braking Distance
Maximum hight of the floor, in which a ogive drive can be done.
Unit: meter
Value range: 0,000 … 5,000 m
Factory setting: 0,000 m
Maximum Hight Of Floor
To provide a good driving comfort the changeover
speed must be decreased. That means: by increasing
the breaking distance the delay point will switch
earlier. To avoid very long crawl drives when the drive
goes over several levels, in parameter LF.71 the delay
described above will be compensated.