LE - Parameter
72
The frequency levels are the comparison values for the frequency dependent output
conditions of the digital outputs. The frequency level is valid for both directions of
rotation. Frequency level 1 is valid for output condition 1 etc. The frequency hysteresis
specifies the switching hysteresis.
Value range: 0 ... 409.5875 Hz
Resolution: 0.0125 Hz
These parameters are the comparison values for the dependent rate of utilization
output conditions of the digital outputs. The loading level is valid for output condition 1
etc.
Value range: 0 ... 200 %
Resolution: 1 %
These parameters are the comparison values for the dependent active current output
condition of the digital outputs. Active current level 1 is valid for output condition 1 etc.
Value range: 0 ... 370 A
Resolution: 0.1 A
If the OL-counter (ru.24) 100% is reached, then the error E.OL is triggered. LE.32 is
the comparison value for the output condition "OL-Warning Level".
Value range: 0 ... 100 %
Resolution: 1 %
Frequency Level
1 -2 (LE. 0 - LE.2)
Frequency
Hysteresis (LE.36)
Load Levels 1 - 2
(LE. 8 - LE.9)
Active Current Level
1 -2 (LE.16 - LE.17)
OL - Warning Level
(LE.32)