Problem Cause/Solution/Troubleshoot
Motor does not go the correct
speed or cannot reach high
speed.
Check whether the Command Speed and Encoder Speed match
(CP27 command speed and CP28 Encoder 1 speed) .
Check Input Status, CP25, to determine whether the correct inputs are
being signaled for a run command.
Check whether the (Voltage) Modulation Grade is reaching 100%. Refer
to Voltage Modulation Grade limited reached for further troubleshooting.
Check if the Inverter Peak Current limit is being reached.
Check if the speed control gains (KP Proportional, KI Integral Offset) are
set too low.
Cannot lift full load Check the motor current and whether the Inverter Peak Current
limit is being reached. Refer to Motor Draws High Current for
additional troubleshooting.
Check if the speed control gains (KP Proportional, KI Integral Offset) are
set too low.
For open loop induction motors, the Low Speed Torque Boost may need
to be increased or decreased if reaching the Inverter Peak Current.
Unable to run induction motor
in open loop.
Low Speed Torque Boost, CP19 may need to be decreased or
increased.
Verify there are no mechanical issues preventing the motor from
rotating freely.
Motor only moves one
direction; direction of
weighting (e.g. full load
escalator in down direction)
Check the motor current. Refer to Motor Draws High Current for
additional troubleshooting.
Check the Command Speed for dictated speed direction and whether it
changes between directions.
Output current is limited
(clamped)
Verify the current is not being limited by the Inverter Peak Current Limit.
Check if motor current is excessive. Refer to Motor Draws High
Current for additional troubleshooting.
Output current is limited
(clamped)
Verify the current is not being limited by the Inverter Peak Current Limit.
Check if motor current is excessive. Refer to Motor Draws High
Current for additional troubleshooting.

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)

Related product manuals