KR-RM Series(13kVA) UPS
User Manual
A Technical Specifications
All rights reserved ©Xiamen Kehua Hengsheng Co., Ltd.
31
Model
Index
KR1000-RM
KR2000-RM
KR3000-RM
mode(ms)
Overload
ability
Low
overload
for 1min
1000VA/900W Load
1300VA/1040W
2000VA/1800W
Load
2600VA/2080W
3000VA/2700W
Load
3900VA/3120W
Medium
overload
for 1s
1300VA/1040WLoad
1500VA/1200W
2600VA/2080W
Load
3000VA/2400W
3900VA/3120W
Load
4500VA/3600W
High
overload
for 200ms
1500VA/1200WLoad
3000VA/2400W
Load
4500VA/3600W
Load
Output receptacles
Four IEC sockets with
10A.
Six IEC sockets with 10A, one IEC socket with
16A
Other features
Backup time
3mins
Charge recovery time
<10 hours
Communication interface
Standard: RS232 and USB port support UPS power management software
Optional: dry contact, SNMP adapter
Display
LCD displays the running status of UPS.
Alarm function
Battery low-voltage, mains abnormal, UPS fault, output overload
Protection function
Battery under-voltage protection, overload protection, short-circuit
protection, over-temperature protection, input over-voltage protection
Noise(dB)
<50
<55
Working temperature()
-540
Relative humidity
095%, non-condensing