Table 2 - Compatible detectors
Model Type Manufacturer Maximum Number per zone
SLR-E/SLR-E3 OPTICAL Hochiki 32
SIJ-E/ IONISATION Hochiki 32
DCD-1E/DCD-AE3 HEAT Hochiki 32
DCD-2E HEAT Hochiki 32
DCD-1RE/DCD-CE3 HEAT Hochiki 32
DFG-60E HEAT Hochiki 32
DFJ-60E/DFJAE3 HEAT Hochiki 32
DFJ90-E/DFJCE3 HEAT Hochiki 32
SPB-ET BEAM Hochiki 8
SRA-ET BEAM Hochiki 5
55000-200/210 - SERIES 60 IONISATION Apollo 32
55000-300 - SERIES 60 OPTICAL Apollo 32
55000-100 - SERIES 60 HEAT Apollo 32
55000-101 - SERIES 60 HEAT Apollo 32
55000-102 - SERIES 60 HEAT Apollo 32
55000-103 - SERIES 60 HEAT Apollo 32
55000-104 - SERIES 60 HEAT Apollo 32
55000-215 -SERIES 65 IONISATION Apollo 32
55000-216 - SERIES 65 IONISATION Apollo 32
55000-217 - SERIES 65 IONISATION Apollo 32
55000-218 - SERIES 65 IONISATION Apollo 32
55000-219 - SERIES 65 IONISATION Apollo 32
55000-220 - SERIES 65 IONISATION Apollo 32
55000-315 - SERIES 65 OPTICAL Apollo 32
55000-316 - SERIES 65 OPTICAL Apollo 32
55000-317 - SERIES 65 OPTICAL Apollo 32
55000-120 - SERIES 65 HEAT Apollo 32
55000-121 - SERIES 65 HEAT Apollo 32
55000-122 - SERIES 65 HEAT Apollo 32
53541-151 - SERIES 30 IONISATION Apollo 32
53541-152 - SERIES 30 IONISATION Apollo 32
53551-101 - SERIES 30 OPTICAL Apollo 32
53531-221 - SERIES 30 HEAT Apollo 28
53531-211 - SERIES 30 HEAT Apollo 28
53531-212 - SERIES 30 HEAT Apollo 28
53531-213 - SERIES 30 HEAT Apollo 28
53531-214 - SERIES 30 HEAT Apollo 28
ORB-OP-12001-APO Optical Apollo 15
ORB-OH-13001-APO Multisensor Apollo 15
ORB-HT-11001-APO A1R Heat Apollo 15
ORB-HT-11002-APO A2S Heat Apollo 15
ORB-HT-11003-APO BR Heat Apollo 15
ORB-HT-11004-APO BS Heat Apollo 15
ORB-HT-11005-APO CR Heat Apollo 15
ORB-HT-11006-APO CS Heat Apollo 15
NID-58 IONISATION Nittan 32
2KC/2KD OPTICAL Nittan 32
2SA-LS/2SA-70T-LS HEAT Nittan 32
TCA-70-LS HEAT Nittan 32
NFD-18-2/NFD-18-5 FLAME Nittan 3
NID-48F IONISATION Nittan 32
NS-12-7 HEAT Nittan 32
NC-9C-70T HEAT Nittan 32
ECO1002 HEAT/PHOTO System Sensor 21
ECO1003 PHOTO System Sensor 26
ECO1005 HEAT System Sensor 22
ECO1005T HEAT System Sensor 22
Although the current consumption of many detection devices would allow more than 32 to be connected to a zone,
this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the
indication of a fire alarm from more than 32 fire detectors and/or call points as required by European standard
EN54-2. If an active end of line LCMU (K14060) is used fit a maximum of 20 detectors per zone.