Man-1112 Sigma XT+_23 Page 25 of 52
The LCD will then display:
STATUS UNIT X X = the address of the remaining status units found
ENTER TO ACCEPT
Or
output unit X X = the address of the remaining ancillary boards unit found
ENTER TO ACCEPT
When the ENTER button is pressed on the module to which the status units or ancillary boards are connected, the
selected status unit or ancillary board will be added to the system and the next unit to be added will be displayed.
Press the ENTER button on the extinguishing module until all of the units have been accepted then gently slide the
WRITE ENABLE on the extinguishing module switch to the right.
Full details of status units and ancillary boards can be found in documents MAN-1089 (Sigma XT Status unit
operation an maintenance manual) and MAN-1095 (Ancillary board operation and maintenance manual).