Menu Navigation (up / down / left / right / enter / exit)
These are used to enter the password for access level 2 and are also used to navigate the Access 2
Facilities Menu.
Help (?)
This button offers additional information relating to the current status of the control panel. e.g. if the
panel is in an alarm or fault condition then advice on the recommended action will be displayed or if a
menu function is being accessed then help relating to that function will be displayed.
3.2 Access Level 2
Access level 2 can be reached by pressing any of the menu navigation buttons. This will then request the
user to enter the correct Access level 2 password (a 4 digit number) followed by the Enter button.
The factory default password for Access level 2 is 2222.
The Access level 2 password can be changed at commissioning to meet customer’s requirements. Enter
the Access level 2 password in the space below for future reference.
Access level 2 will be required by the end user to acknowledge alarms and reset the system.
Any persons responsible for the fire alarm system should be aware of the access level 2 password to
enable the panel controls.
Without this password it will not be possible to acknowledge alarms or reset the system so it is most
important that the responsible person knows the password.
Silence Alarm / Acknowledge
This button is normally used to mute any fire warning sounders fitted to the Syncro panel. These sounders
are installed throughout the protected premises and are used to evacuate the premises.
In some cases, the fire warning sounders may be delayed; to allow a search time before building
evacuation commences. In this case, the “Delay Active” panel indicator will be illuminated. If the
Acknowledge Alarm button is pressed during the Delay Active period, the sounders may either be
permanently muted or the delay may be extended to the second stage delay time. This will depend upon
the panel configuration and cannot be amended by the end user.
If there is a second fire activation during an Active Delay, then all delays are cancelled and outputs will
operate in accordance with the building fire strategy.
Re-sound Alarm
If any fire warning sounders have been muted using the Acknowledge Alarm button, then pressing the Re-
sound Alarm will re-energise all muted sounders.
Reset
This button is used to reset any activation that is defined as a latching input type. These will include fire
and pre-alarm events. In general, fault events are non-latching and cannot be cleared by operation of the
Reset button. These events will clear when the fault input is cleared.
Function 1 & 2
These two buttons are software programmable inputs that may be used to perform customer-defined
actions. The default operation of these buttons is to perform no action (transparent input).
The operation of these buttons should be entered in the box below;
ACCESS 2 PASSWORD ………………………….
Function 1 button ……………………………………………………
……………………………………………………
Function 2 button ……………………………………………………
……………………………………………………