3-10 Setup Procedure For The Batcher
3-10 Setup Procedure For The Batcher
MENU ITEM 1
PRESET
PRESS
DISPLAY
PRESET
Menu Button.
Flashing PRESET number.
Enters Preset Routine.
0 Flashes.
Clears out existing PRESET.
1234 PRESET Flashes.
Sample Preset.
Last count, unit now in run mode.
Store new Preset.
Final Preset is Set.
MENU ITEM 2
PREWARN
The Prewarn value is the amount
before
the Preset value that the Prewarn relay will deactivate. For example, if
you want the Prewarn relay to drop out 10 counts before the Preset and your Preset is 1234, then set your Prewarn
at 10 (not at 1224). Enter a Prewarn of “0” for the Prewarn and Preset relays to activate together. To disable the
Prewarn relay, enter the same value for Preset and Prewarn.
PRESS
DISPLAY
PRESET
MENU Button.
PREWARN
Flashing PREWARN number.
Enters Prewarn Routine.
0 Flashes.
Clears out existing PREWARN.
1234 Prewarn Flashes.
Sample Prewarn.
Last count, unit now in Run Mode.
Store new Prewarn.
The Prewarn is Set.
Note: Remember, if the prewarn is a larger number than the preset, then the warning “
PREWRONG
” will ash on
the display. Enter a prewarn value that is less than or equal to the preset to clear this warning.
D
CLR
ENT
1 2 3 4
ENT
D
D
ENT
CLR
1 2 3 4
ENT