3-10 Setup Procedure For The Batcher
3-10 Setup Procedure For The Batcher
This section is for models of the Batcher which have 16 Point Linearization.
lows the user to key in from 3 to 16 different frequency points (inputs per second) and
assign different K Factors dividers from 0.00011 to 999999 for each of these frequen-
Please refer to the K Factor worksheets (Section 7) or other notes you may have prepared.
Please refer to the K Factor worksheets (Section 7) or other notes you may have prepared.
Press until . . . 16 POINT
The unit calculates the base rate per second from the incoming frequency and the spec-
ifi ed K Factor. The rate can then be displayed in 3 ways:
MINUTES: The base rate times 60.
HOURS: The base rate times 3600.
TEST is used to help set up the points and K Factors. In this mode the K Factor is au-
tomatically set to (1) one for both rate and total for all 16 points. Further information on
this mode can be found in Section 7-3 of this manual.
Press ENT on desired rate display. The unit now enters the Frequency and K Factor
To escape from this mode, press
To escape from this mode, press
when POINT 00 is being displayed.
when POINT 00 is being displayed.
Enter any other point from 1 to 16 via the front keypad and press ENT to continue.
Note: If the point number entered is greater than 16, the unit will default back to point