6. Recommended Locations for CO Alarms
Note: CO alarms should be installed following the guidance of relevant local standards, such as
EN50292.
Whether the alarm is wall-mounted or ceiling mounted, place the alarm a horizontal distance of
between 1 metre and 3 metres from a fuel burning appliance.
When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a mini-
mum of 150 mm below the ceiling. The bottom of the alarm should also be at a level greater than
the height of any door or window.
Locate within hearing distance of bedrooms* and place at sleeping height if a heating appliance is
in the bedroom.
CO alarms in rooms with sloped ceilings should be located on the high side of the room.
Ceiling mounted alarms should be at least 300 mm from any wall.
If there is a partition in the room, locate the alarm on the same side of the partition as the potential
source.
* A CO alarm should be installed in all rooms containing a fuel burning appliance. Additional CO
alarms should be installed in rooms where most awake time is spent, in every sleeping area, and
on every level of the home.
2030-7202-01_2030-DCR_UG_54x96_TUV_80%.indd 112030-7202-01_2030-DCR_UG_54x96_TUV_80%.indd 11 22-1-7 3:1722-1-7 下午3:17

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde 2030-DCR and is the answer not in the manual?

Kidde 2030-DCR Specifications

General IconGeneral
BrandKidde
Model2030-DCR
CategorySecurity System
LanguageEnglish

Related product manuals