Chapter 1 Product design
6 GSA-REL Technical Reference Manual
Table 3: FM requirements for automatic fire extinguishing systems
Specification
Value
Standby operation
24 hours
Alarm operation
10 minutes
NFPA style
B or D
FM documentation
FMRC Approval Guide (Volume 1)
Compatible panels and devices
Panels
The GSA-REL is compatible with MIR2 and QuickStart fire alarm control panels.
The GSA-REL must be installed in an enclosure dedicated to the releasing
system. No other devices may be installed in the enclosure. You can install the
GSA-REL in any of the following enclosures:
2-WB series
MFC-A
RACCR series
Maintain a 1-inch (25.4 mm) minimum clearance all around the GSA-REL. The
clearance space must also comply with NFPA 70, the National Electrical Code.
Software
You will need the latest version of the system definition utility or configuration
utility for your MIR2 or QuickStart system. These are available from our website:
For MIR2: 2-SDU
For QuickStart: QS-CU