Chapter 1: Product design
GSA-REL Technical Reference Manual 11
Signature data line, TB1
Operating voltage
Supervisory current
Alarm current
Line resistance
Maximum quantity
15.2 to 19.95 VDC
1 mA
1 mA
See the installation sheet for the Signature loop controller
10 GSA-REL modules per loop
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
[1] Riser current: The total current of the prerelease and release circuits is limited to 3.83 A. This
is the power riser maximum input current of 4 A, minus 170 mA.
Table 7: Power riser
Distance from GSA-REL to power supply
[1] Wire resistance measured in Ω per wire
Table 8: Prerelease and release circuits (per circuit)
Distance from GSA-REL to signals
[1] Wire resistance measured in Ω per wire