P/N 3102382-EN • REV 02 • ISS 15DEC16 11
Specifications
24 VDC, continuous. Do not use control panel AUX
power outputs that are interrupted when the panel is
reset. Supply must be UL/ULC Listed for use with fire
protective signaling systems and have a rating
designation of Regulated 24 DC or Regulated 24 FWR.
K-RLCD, K-RLCDF, K-RLCD-R,
K-RLCD-PG, K-RLCD-SP
K-RLCD-C, K-RLCD-CF, K-RLCD-CR,
K-RLCD-C-PG, K-RLCD-C-SP
K-RLED-C, K-RLED-CF, K-RLED-CR,
K-RLED-C-PG, K-RLED-C-SP
K-RLED24, K-RLED24R
98 mA
99 mA
28 mA
6 mA
K-RLCD, K-RLCDF, K-RLCD-R,
K-RLCD-PG, K-RLCD-SP
K-RLCD-C, K-RLCD-CF, K-RLCD-CR,
K-RLCD-C-PG, K-RLCD-C-SP
K-RLED-C, K-RLED-CF, K-RLED-CR,
K-RLED-C-PG, K-RLED-C-SP
K-RLED24, K-RLED24R
113 mA
115 mA
62 mA
34 mA
Class/Style
Wire size
Type
Length
Baud rate
Class B, Redundant Class B, or Class A
14 to 18 AWG (1.0 to 2.5 mm²)
Twisted pair, 6 twists per ft. min.
4,000 ft. (1,219 m), max.
9600 to 115200 baud
Remote key switch circuit
5 VDC at 1 mA, power-limited, unsupervised
0 Ω
14 to 18 AWG (1.0 to 2.5 mm²)
4 lines of 20 characters each
5-5/8 x 8-1/2 x 1-1/2 in. (14.3 x 21.4 x 3.8 cm)
North American 4 in. square electrical box or listed
enclosure (see Table 2)
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing