10 P/N 3102382-EN • REV 02 • ISS 15DEC16
Troubleshooting
When a K-R Series annunciator is operating correctly, the Trouble LED follows the panel’s Trouble LED.
Annunciators with LCD displays show the same trouble messages as the panel. See the topic “Reading LCD
displays” on page 16 for details about message displays.
The following table summarizes symptoms and solutions for common installation and operation problems.
Table 5: K-R Series troubleshooting
Cause
Panel detail display: Annunciator 000
Communication Fault
Communication wiring has an open fault
Communication wiring polarity is reversed
Annunciator has no power
Annunciator address DIP switches are set incorrectly (on the
annunciator shown in the panel message)
Annunciator network baud rate DIP switch is set incorrectly (for
normal operation use 9600 baud)
Annunciator bus type DIP switch is set incorrectly (change S1-
to the other position)
Annunciator LCD and LEDs are inoperative
Annunciator has no power
Annunciator control switches don’t work
Remote key switch is in the “locked” or disabled position
Password entry may be required (see “Entering a password“
page 18)
During a lamp test the annunciators with LCDs show the version
of annunciator firmware currently loaded